Inspections for the day of: Friday, April 6, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRuss Owen
TitleBLD-COM/RES INSPECTOR
Phone #794-9473
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-00805 BLD-Footing4/5/20014/6/20014/6/2001 12:00:00 AMAPASS
ft insp john =###-#### 4 footings ok. 4/6/2001 11:08:39 AM
BLD01-00217 BLD-Framing/Rough-in4/5/20014/6/20014/6/2001 12:00:00 AMAPASS
Greg Hunter ###-####
BLD01-00369 BLD-Framing/Rough-in4/5/20014/6/20014/6/2001 12:00:00 AMAFAIL
###-#### no approved plans,on site work started with out permits no inspections done by ele,mec,plm talked Brian job cont,told him to get plans and recall insp. 4/6/2001 10:27:52 AM 4/6/2001 10:29:08 AM
BLD00-03194 BLD-Concrete4/5/20014/6/20014/6/2001 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 04/05/2001 at 17:26:18. Contact: . MTI on site for lower elevator shaft of elevator. 4/6/2001 12:03:29 PM
BLD01-00333 BLD-Energy code compliance4/6/20014/6/20014/6/2001 12:00:00 AMPPART
Johnny ###-#### 4/6/2001 4:32:43 PM c/n posted for left unit. 4/6/2001 4:34:04 PM
BLD01-00128 BLD-Final4/6/20014/6/20014/6/2001 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 04/06/2001 at 08:38:25. Contact: ###-####.
BLD00-03580 BLD-Foundation4/6/20014/6/20014/6/2001 12:00:00 AMPPART
FOUND WALL-KELLY -- ###-#### 3 int slab footings, and trash enclosure 4/6/2001 4:17:07 PM
BLD01-00369 BLD-Framing/Rough-in4/6/20014/6/20014/6/2001 12:00:00 AMPFAIL
###-####. Went out to reveiw approved plans , all areas have been sheetrocked on 1 side and ceilings also rocked, right rear area requires a 1 hour wall separation and a 2 hour ceiling, for containment of stored battery ,the ceiling joist are not per plan also listed assembly requires laminating compoud at the 3 sheetrock layers, The first layer has been painted with a textured seal coating, which will affect the system, 2nd layer has been applied by screws only, advised contractor to contact the architect and engineer. Also note there has not been any electrical,plumbing or mechanical inspections done at this time.. 4/6/2001 4:44:57 PM 4/6/2001 4:45:26 PM 4/6/2001 4:45:48 PM 4/6/2001 4:48:39 PM