ELE06-00053
| ELE-Aging Inspection | 4/6/2006 | 4/6/2006 | 4/10/2006 8:45:39 AM | | PASS |
|
|
|
ELE05-04498
| Rough-In Permanent Service | 4/6/2006 | 4/6/2006 | 4/6/2006 4:03:29 PM | P | PART |
|
|
barbara ###-####//final insp was supposed to be R/I ok only no p/s corr. 250.24(A)(1) shall terminate GEC at neutral bus not equip. grd. bus called
|
ELE05-04498
| Final | 4/6/2006 | 4/6/2006 | 4/6/2006 4:00:14 PM | P | CANC |
|
|
Thanks for you patience on this project. It's been a real trial for all of us.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
ELE06-01176
| Electrical Rough-In | 4/6/2006 | 4/6/2006 | 4/6/2006 3:26:43 PM | P | NR |
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong needs to wire home theater room outlet spacing walls, low voltage wire not complete needs cabinet installed nail plates 11/4" strap cables
|
ELE06-01166
| Electrical Rough-In | 4/5/2006 | 4/6/2006 | 4/6/2006 2:42:39 PM | A | FAIL |
|
|
###-#### - mike Note: not until after 9:00 am please corr. called partial notice only 300.4 nail plates & 11/4", 110.14(A) seal KOs, 300.15(C) needs conn. for ENT both ends, BCC no violations retained
|
ELE06-00937
| Final | 4/6/2006 | 4/6/2006 | 4/6/2006 1:45:23 PM | P | PART |
|
|
HZ; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/o ok card signed,, corr. called seal KOs 1 in panel breaker seal, 1 on ceiling 4sq box 1/2, 408.4 needs panel schedule
|
ELE05-02538
| Final | 4/6/2006 | 4/6/2006 | 4/6/2006 1:07:48 PM | P | PASS |
|
|
Final inspection for the afternoon of 04/06/06. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie ok card signed
|
ELE05-04546
| ELE-Aging Inspection | 4/6/2006 | 4/6/2006 | 4/6/2006 12:30:25 PM | | PART |
|
|
stopped at job site wsuc
|
ELE05-04497
| ELE-Aging Inspection | 4/6/2006 | 4/6/2006 | 4/6/2006 12:00:18 PM | | PART |
|
|
called contractor will schedule final inspection they just finished completing job
|
ELE06-01125
| Electrical Rough-In | 4/5/2006 | 4/6/2006 | 4/6/2006 10:58:53 AM | A | PASS |
|
|
house will be open at 8; Phone #: ###-#### Internet Inspection Request from: steven sewell basement wiring ok
|
ELE05-04556
| Final | 4/5/2006 | 4/6/2006 | 4/6/2006 10:47:32 AM | A | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr. called 210.52(A&B) needs outlets in kit left of pantry door, and left of counter in nook by stair rails for wall space, 110.3(B) j tub manufactures requires 15"X20" access, 210.8 needs gfci outlet countertop butlers pantry, 250.104(A)(1) and 250.66 needs to bond copper water to p/s and bond hot and cold with #2 copper
|
ELE06-01169
| Temporary Service | 4/5/2006 | 4/6/2006 | 4/6/2006 9:35:43 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corr. called 250.24(A)(1) terminate GEC too neutral bus, 312.5 needs conn. for GEC
|
ELE05-04493
| Final | 4/5/2006 | 4/6/2006 | 4/6/2006 9:02:32 AM | A | PASS |
|
|
Please final Orchards at Fairview monument sign Internet Inspection Request from: Radon Elaina corr. made ok
|
ELE05-04498
| Rough-In Permanent Service | 4/5/2006 | 4/6/2006 | 4/6/2006 8:33:51 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corrections not made still needs nail plates, and 250.24(A)(1) GEC shall terminate too neutral bus not equip grd bus called
|