Inspections for the day of: Friday, April 6, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00653 FIRE-Final Inspection4/6/20074/6/20074/6/2007 8:14:49 PMPPASS
Noted corrections are finished, fire life safety finaled.
FIR07-00296 INSP-Final Inspection4/6/20074/6/20074/6/2007 8:13:43 PMPPASS
Fire alarm permit finaled.
FIR07-00232 INSP-Sprinkler Rough-in/Hydro4/6/20074/6/20074/6/2007 8:10:57 PMPNR
UG fire supply line not yet completed for cover inspection as scheduled due to site conditions.
BLD07-00468 FIRE-Final Inspection4/6/20074/6/20074/6/2007 2:56:58 PMPFAIL
Need to provide one fire extinguisher with current tag mounted on the wall as discussed, missing suite address numbers, locking hardware at the doors to the shared restrooms must allow for egress at one location.
FIR07-00296 INSP-Alarm Testing4/6/20074/6/20074/6/2007 2:39:49 PMPPASS
Noted defficiencies corrected while on site, inspection passed, contractor to update the map at the panel to indicate address and location of the duct detectors.
FIR07-00034 INSP-Sprinkler Rough-in/Hydro4/5/20074/6/20074/6/2007 2:00:22 PMAPART
Cursory inspection of the basement overhead rough-in, contractor could not locate approved plans on site, noted two SW heads which exceed min. spacing allowance, need to reinspect with stamped plan set on site as required.
FIR07-00080 INSP-Final Inspection4/5/20074/6/20074/6/2007 1:53:47 PMPCANC
Please call as soon as you know about when you can be on-site. Thank You. Jason Phone #: ###-#### Inspection cancelled from web by: Jason Minnick
BLD06-00660 FIRE-Final Inspection4/5/20074/6/20074/6/2007 11:29:25 AMAPASS
Fire life safety final inspection passed.
FIR06-00698 INSP-Final Inspection4/5/20074/6/20074/6/2007 11:28:30 AMAPASS
Fire sprinkler permit finaled.
BLD05-02651 FIRE-Final Inspection4/5/20074/6/20074/6/2007 11:10:00 AMAPASS
Necessary corrections have been verified, final fire life safety inspection passed.
BLD06-02208 FIRE-Final Inspection4/5/20074/6/20074/6/2007 11:07:22 AMAFAIL
Missing PFE's on level one and two as indicated on review notes and and stamped plans, door hardware at the second floor doors are not approved.
FIR07-00211 INSP-Sprinkler Rough-in/Hydro4/4/20074/6/20074/6/2007 11:04:49 AMANR
Plans are not completed for inspection, installation work appears satisfactory.
FIR06-00742 INSP-Sprinkler Rough-in/Hydro4/4/20074/6/20074/6/2007 11:02:08 AMAPART
OH fire sprinkler rough-in at 103 B4 is approved for cover, final pending ceiling tile and escutcheons.