BLD06-00653
| FIRE-Final Inspection | 4/6/2007 | 4/6/2007 | 4/6/2007 8:14:49 PM | P | PASS |
|
|
Noted corrections are finished, fire life safety finaled.
|
FIR07-00296
| INSP-Final Inspection | 4/6/2007 | 4/6/2007 | 4/6/2007 8:13:43 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00232
| INSP-Sprinkler Rough-in/Hydro | 4/6/2007 | 4/6/2007 | 4/6/2007 8:10:57 PM | P | NR |
|
|
UG fire supply line not yet completed for cover inspection as scheduled due to site conditions.
|
BLD07-00468
| FIRE-Final Inspection | 4/6/2007 | 4/6/2007 | 4/6/2007 2:56:58 PM | P | FAIL |
|
|
Need to provide one fire extinguisher with current tag mounted on the wall as discussed, missing suite address numbers, locking hardware at the doors to the shared restrooms must allow for egress at one location.
|
FIR07-00296
| INSP-Alarm Testing | 4/6/2007 | 4/6/2007 | 4/6/2007 2:39:49 PM | P | PASS |
|
|
Noted defficiencies corrected while on site, inspection passed, contractor to update the map at the panel to indicate address and location of the duct detectors.
|
FIR07-00034
| INSP-Sprinkler Rough-in/Hydro | 4/5/2007 | 4/6/2007 | 4/6/2007 2:00:22 PM | A | PART |
|
|
Cursory inspection of the basement overhead rough-in, contractor could not locate approved plans on site, noted two SW heads which exceed min. spacing allowance, need to reinspect with stamped plan set on site as required.
|
FIR07-00080
| INSP-Final Inspection | 4/5/2007 | 4/6/2007 | 4/6/2007 1:53:47 PM | P | CANC |
|
|
Please call as soon as you know about when you can be on-site. Thank You. Jason Phone #: ###-#### Inspection cancelled from web by: Jason Minnick
|
BLD06-00660
| FIRE-Final Inspection | 4/5/2007 | 4/6/2007 | 4/6/2007 11:29:25 AM | A | PASS |
|
|
Fire life safety final inspection passed.
|
FIR06-00698
| INSP-Final Inspection | 4/5/2007 | 4/6/2007 | 4/6/2007 11:28:30 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-02651
| FIRE-Final Inspection | 4/5/2007 | 4/6/2007 | 4/6/2007 11:10:00 AM | A | PASS |
|
|
Necessary corrections have been verified, final fire life safety inspection passed.
|
BLD06-02208
| FIRE-Final Inspection | 4/5/2007 | 4/6/2007 | 4/6/2007 11:07:22 AM | A | FAIL |
|
|
Missing PFE's on level one and two as indicated on review notes and and stamped plans, door hardware at the second floor doors are not approved.
|
FIR07-00211
| INSP-Sprinkler Rough-in/Hydro | 4/4/2007 | 4/6/2007 | 4/6/2007 11:04:49 AM | A | NR |
|
|
Plans are not completed for inspection, installation work appears satisfactory.
|
FIR06-00742
| INSP-Sprinkler Rough-in/Hydro | 4/4/2007 | 4/6/2007 | 4/6/2007 11:02:08 AM | A | PART |
|
|
OH fire sprinkler rough-in at 103 B4 is approved for cover, final pending ceiling tile and escutcheons.
|