Inspections for the day of: Monday, April 6, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00097 INSP-Sprinkler Rough-in4/6/20094/6/20094/7/2009 1:09:37 PMPCANC
wrong permit called in.
FIR05-00648 INSP-Final Inspection4/6/20094/6/20094/6/2009 3:05:32 PMPPASS
Permit finaled
FIR09-00031 INSP-Sprinkler Rough-in/Hydro4/6/20094/6/20094/6/2009 3:03:40 PMPPART
24 hour air test started at 8:30 with 51psi on the guage.
BLD08-01467 FIRE-Final Inspection4/5/20094/6/20094/6/2009 3:02:33 PMAPASS
Life safety passed.
FIR08-00607 INSP-Final Inspection4/6/20094/6/20094/6/2009 3:01:58 PMPPASS
Permit finaled. It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
FIR08-00607 INSP-Alarm Testing4/6/20094/6/20094/6/2009 3:00:16 PMAPASS
It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
FIR09-00096 INSP-Alarm Testing4/3/20094/6/20094/6/2009 12:55:46 PMAPART
Todays inspection was for the fire alarm rough-in for the 3rd floor of building "B". The rough-in in general passed except that the horns in the rooms are not mounted at the correct heights as per NFPA 72 - 7.4. Per a conversation with Mike the strobes will be relocated to meet code requirements. Also no fixtures have been installed which may cause obstruction problems.
FIR09-00125 INSP-Sprinkler Rough-in/Hydro4/6/20094/6/20094/6/2009 11:19:16 AMAFAIL
The overhead hydro test failed due to atleast two observed leaks/puddles on the floor.
BLD09-00340 FIRE-Final Inspection4/3/20094/6/20094/6/2009 10:00:51 AMAPASS
Life safety passed.
BLD08-02587 FIRE-Final Inspection4/3/20094/6/20094/6/2009 9:41:02 AMAPASS
life safety passed