Inspections for the day of: Tuesday, April 6, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02299 FIRE-Conference4/6/20104/6/20104/7/2010 7:55:32 AMPDONE
I received a phone call and an email from Patrick the architect about the Kraft backing on the insulation. I deferred him to the building plan reviewer and the structural inspector for any approvals.
BLD10-00228 FIRE-Conference4/5/20104/6/20104/7/2010 7:51:44 AMADONE
The builder was questioning door hardware on the southwest exit door. Single action is required and the thumbturn dead bolt needs to be removed.
BLD10-00395 FIRE-Final Inspection4/6/20104/6/20104/6/2010 2:50:17 PMPPASS
Life safety passed
BLD10-00649 FIRE-Final Inspection4/6/20104/6/20104/6/2010 2:49:47 PMPFAIL
Provide annual inspection for the fire extinguisher, provide address as discussed and cover the exposed electrical outlets.
FIR09-00013 INSP-Final Inspection4/5/20104/6/20104/6/2010 11:23:42 AMAFAIL
The AES panel only had a Netcon 6. No inspection performed.
FIR09-00012 INSP-Final Inspection4/5/20104/6/20104/6/2010 11:23:27 AMAFAIL
The AES panel only had a Netcon 6. No inspection performed.
FIR10-00141 INSP-Sprinkler Rough-in4/5/20104/6/20104/6/2010 11:22:36 AMAFAIL
Four pendant heads exceed the maximum calculated of 8' off of walls. Also the underground sprinkler piping is poly plastic not copper as per the drawings. Also the area marked "Storage" is now an exterior covered patio with the sprinkler protection deleted.
FIR10-00139 INSP-Sprinkler Rough-in4/5/20104/6/20104/6/2010 11:20:37 AMAFAIL
Per the city approved plans the new branchline that feeds the two new pendants is to be sized at 1 1/4". It has been installed as a 1 1/4" starter piece and then reduces to 1".