Inspections for the day of: Monday, April 6, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00015 INSP-Final Inspection4/6/20154/6/20154/6/2015 4:19:47 PMPCANC
Overbooked. Inspection will need to be rescheduled. Tried to leave message on contacts voice mail. Cole Phone #: ###-####
FIR14-00620 INSP-Sprinkler Rough-in4/3/20154/6/20154/6/2015 4:09:01 PMPCANC
Overbooked
BLD14-03296 FIRE-Final Inspection4/6/20154/6/20154/6/2015 4:04:44 PMPFAIL
Provide panic hardware at the main exit as per approved plans, provide correct annunciator for the duct smoke detector and repair the exit sign at the rear exit. Provide city approved plans.
FIR15-00138 INSP-Sprinkler Rough-in/Hydro4/6/20154/6/20154/6/2015 3:44:35 PMPPASS
Permit finaled
FIR14-00872 INSP-Final Inspection4/6/20154/6/20154/6/2015 3:27:43 PMPPASS
Permit finaled
BLD15-01034 FIRE-Final Inspection4/3/20154/6/20154/6/2015 2:21:40 PMAFAIL
Provide address, remove thumbturn lock and provide sticker at the main exit, provide fire extinguisher with current inspection tag.
FIR15-00145 INSP-Final Inspection4/3/20154/6/20154/6/2015 1:21:42 PMAPASS
Permit finaled. Hood suppression system functioned correctly.
FIR15-00164 INSP-Final Inspection4/6/20154/6/20154/6/2015 11:18:25 AMPPASS
Permit finaled
BLD15-00118 FIRE-Final Inspection4/3/20154/6/20154/6/2015 11:15:43 AMAFAIL
Need permit showing security tie in with the fire alarm system. Also verification that sensor is not required for the access controled egress door.
BLD15-00480 FIRE-Final Inspection4/3/20154/6/20154/6/2015 11:14:31 AMAPART
Life safety passed on fourth floor only. Life safety will be ok to pass for basement scope of work wient permit is issued/passed for access control egress doors interconnection permit with the existing fire alarm system. This new work will require a permit.
FIR15-00199 INSP-Final Inspection4/3/20154/6/20154/6/2015 11:14:26 AMAPASS
Permit finaled. This permit scope of work was for fourth floor only.
BLD14-03629 FIRE-Final Inspection4/3/20154/6/20154/6/2015 9:38:08 AMAPASS
Life safety passed. I spoke to contractor about the thumb turn locks on the security grills and the need to be keyed prior to the building inspection.
FIR15-00070 INSP-Final Inspection4/3/20154/6/20154/6/2015 9:32:55 AMAPASS
permit finaled
FIR15-00060 INSP-Final Inspection4/3/20154/6/20154/6/2015 9:32:24 AMPPASS
Permit finaled
FIR15-00128 INSP-Final Inspection4/3/20154/6/20154/6/2015 12:00:00 AMPPASS
final inspection of weatherproof device in shower complete / approved.