Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00709 INSP-Sprinkler Rough-in4/6/20164/6/20164/6/2016 2:21:50 PMPDONE
Today was more of a conference. Robert and I discussed earth quake bracing attachment for the stand pipes. He also relocated the pendant in the Roof Access room for better coverage.
FIR15-00822 INSP-Sprinkler Rough-in4/6/20164/6/20164/6/2016 2:01:16 PMPPASS
See the city approved plans for piping marked "ok" whre piping above hard lids can be covered.
BLD16-00332 FIRE-Conference4/6/20164/6/20164/6/2016 1:17:53 PMPDONE
The builder contacted me to ask what size of access door would be required for access to the existing anti-freeze loop equipment. I referred him to IFC 509.3
FIR16-00226 INSP-Sprinkler Rough-in4/5/20164/6/20164/6/2016 10:46:01 AMAPASS
Piping above hard lids is ok to cover.
BLD16-00619 FIRE-Final Inspection4/5/20164/6/20164/6/2016 10:36:17 AMAFAIL
Need city approved plans and notes, need ceiling tile installed for the sprinkler heads, need doors and hardware installed, need fire alarm modifications due to the new corridor addition.
FIR16-00153 INSP-Final Inspection4/5/20164/6/20164/6/2016 10:32:25 AMAFAIL
Ceiling tile not installed yet.