BLD17-00486
| FIRE-Final Inspection | 4/5/2017 | 4/6/2017 | 4/6/2017 1:46:37 PM | P | PASS |
|
|
Life safety passed
|
FIR17-00136
| INSP-Sprinkler Rough-in | 4/6/2017 | 4/6/2017 | 4/6/2017 1:39:16 PM | P | PASS |
|
|
Hard lids ok for cover
|
BLD16-02646
| FIRE-Final Inspection | 4/5/2017 | 4/6/2017 | 4/6/2017 1:37:44 PM | A | PASS |
|
|
Life safety passed.
|
FIR16-00824
| INSP-Sprinkler Rough-in | 4/6/2017 | 4/6/2017 | 4/6/2017 1:37:17 PM | P | PASS |
|
|
Re-routing of the underground piping has been approved. All sprinkler piping in the building can be covered.
|
FIR16-00823
| INSP-Sprinkler Rough-in | 4/6/2017 | 4/6/2017 | 4/6/2017 1:37:16 PM | P | FAIL |
|
|
The city approved plans for the rerouted underground supply piping have been provided but they do not match the actual installation. Revised plans showing the actual placement of pipe need to be provided to plan review. Second floor piping is still not tented yet.
|
FIR16-00284
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/6/2017 | 4/6/2017 9:43:58 AM | A | PASS |
|
|
Unit 201 piping above soffits can be covered
|
FIR17-00115
| INSP-Sprinkler Rough-in | 4/5/2017 | 4/6/2017 | 4/6/2017 9:41:58 AM | A | PASS |
|
|
Piping above hardlids is ok for cover.
|