ELE18-00993
| Final | 4/6/2018 | 4/6/2018 | 4/6/2018 2:21:06 PM | P | PASS |
|
|
Inspection requested via web by Steve Craig No card posted. Final ok
|
ELE18-01274
| Final | 4/6/2018 | 4/6/2018 | 4/6/2018 2:20:35 PM | P | PASS |
|
|
2nd permit pulled for same job. No card posted. Final ok
|
ELE18-00286
| Final | 4/6/2018 | 4/6/2018 | 4/6/2018 2:15:29 PM | P | FAIL |
|
|
Lock box code 4888 Phone #: ###-#### Inspection requested via web by Lars Johnson 210.52(C)(1)- Receptacle to serve counter top to left of range blocked by range. Relocated over counter to be served.
|
ELE18-01205
| Electrical Rough-In | 4/5/2018 | 4/6/2018 | 4/6/2018 1:01:41 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Duplicate request
|
ELE18-01331
| Electrical Rough-In | 4/6/2018 | 4/6/2018 | 4/6/2018 12:55:02 PM | P | PASS |
|
|
underground- Mark Phone #: ###-#### 36" on feed to new distibution location and 24" to new additional emergency switch location, underground rough in ok cover.
|
ELE18-01205
| Electrical Rough-In | 4/5/2018 | 4/6/2018 | 4/6/2018 11:58:00 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton South corridor, break room, west corridor hardlids and west soffit rough in ok cover
|
ELE18-00782
| Electrical Rough-In | 3/30/2018 | 4/6/2018 | 4/6/2018 10:43:03 AM | A | PASS |
|
|
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Listing confirmed rough in ok
|
ELE18-01327
| Temporary Service | 4/5/2018 | 4/6/2018 | 4/6/2018 10:09:57 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 250.66- Minimum conductor shall be fully terminated. Appox 1/2 of strands balled up not entering terminal in meter enclosure.
|
ELE18-00665
| Electrical Rough-In | 4/5/2018 | 4/6/2018 | 4/6/2018 9:46:00 AM | A | FAIL |
|
|
Any questions please call Jordan @ ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller 300.4- MC cable shall not be secured with in 1 1/4" from framing surface. 314.23- Junction boxes shall be securely mounted in place. 314.29- Boxes shall be accessible. Boxes above hardlid shall have an access panel or be relocated. 330.30- MC cable shall be secured with in 12" of a box.
|