Inspections for the day of: Friday, April 6, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00993 Final4/6/20184/6/20184/6/2018 2:21:06 PMPPASS
Inspection requested via web by Steve Craig No card posted. Final ok
ELE18-01274 Final4/6/20184/6/20184/6/2018 2:20:35 PMPPASS
2nd permit pulled for same job. No card posted. Final ok
ELE18-00286 Final4/6/20184/6/20184/6/2018 2:15:29 PMPFAIL
Lock box code 4888 Phone #: ###-#### Inspection requested via web by Lars Johnson
210.52(C)(1)- Receptacle to serve counter top to left of range blocked by range. Relocated over counter to be served.
ELE18-01205 Electrical Rough-In4/5/20184/6/20184/6/2018 1:01:41 PMPCANC
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Duplicate request
ELE18-01331 Electrical Rough-In4/6/20184/6/20184/6/2018 12:55:02 PMPPASS
underground- Mark Phone #: ###-####
36" on feed to new distibution location and 24" to new additional emergency switch location, underground rough in ok cover.
ELE18-01205 Electrical Rough-In4/5/20184/6/20184/6/2018 11:58:00 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
South corridor, break room, west corridor hardlids and west soffit rough in ok cover
ELE18-00782 Electrical Rough-In3/30/20184/6/20184/6/2018 10:43:03 AMAPASS
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Listing confirmed rough in ok
ELE18-01327 Temporary Service4/5/20184/6/20184/6/2018 10:09:57 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.66- Minimum conductor shall be fully terminated. Appox 1/2 of strands balled up not entering terminal in meter enclosure.
ELE18-00665 Electrical Rough-In4/5/20184/6/20184/6/2018 9:46:00 AMAFAIL
Any questions please call Jordan @ ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller
300.4- MC cable shall not be secured with in 1 1/4" from framing surface.
314.23- Junction boxes shall be securely mounted in place.
314.29- Boxes shall be accessible. Boxes above hardlid shall have an access panel or be relocated.
330.30- MC cable shall be secured with in 12" of a box.