GRD17-00082
| FIRE-Final Inspection | 4/5/2018 | 4/6/2018 | 4/10/2018 7:18:02 AM | P | PASS |
|
|
Life safety passed. Both gates have been modified for the 20' width
At Quality Electric offices. Contact is either Don Rye or Jay Hintze. Phone #: ###-#### Inspection requested via web by Scott Campbell
|
FIR18-00242
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 1:39:44 PM | P | PASS |
|
|
Permit finaled
|
FIR17-00460
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 1:22:15 PM | P | CANC |
|
|
Unable to test the sprinkler devices due to fire alarm issues. Contractor needs to verify that the shipping clips have been removed from heads.
|
FIR17-00461
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 1:22:01 PM | P | CANC |
|
|
Unable to test the sprinkler devices due to fire alarm issues. Contractor needs to verify that the shipping clips have been removed from heads.
|
FIR17-00493
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 1:20:53 PM | P | FAIL |
|
|
Resubmit plans showing the correct dialer/communicator and the correct zone arrangement. Will need to test all devices.
|
FIR17-00492
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 1:20:32 PM | P | FAIL |
|
|
Resubmit plans showing the correct dialer/communicator and the correct zone arrangement. Will need to test all devices.
|
BLD18-00584
| FIRE-Final Inspection | 4/6/2018 | 4/6/2018 | 4/6/2018 12:32:34 PM | P | PASS |
|
|
Life safety passed. Contractor is going to install the correct single action hardware on the doors as discussed.
Elliot Phone #: ###-####
|
FIR17-00668
| INSP-Final Inspection | 4/4/2018 | 4/6/2018 | 4/6/2018 10:54:09 AM | A | FAIL |
|
|
The head end equipment was tested. Netcon was a 5. Batteries match and a dedicated circuit has been provied. No sprinkler devices have been tested due to the sprinkler contractor not showing up. We tested duct smoke detectors in multiple tenant spaces and I noted in one space the duct smoke detector did not shut down immediatley as required. Also plan modifications are needed to show the notification devices in the two riser rooms and through out the day care. The ground wire for the AES has not been installed either.
Laura -call for access--owner and Jim from American Fire, and keith, colliers, peter from crane alarm Phone #: ###-####
|
BLD17-04482
| FIRE-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 9:46:05 AM | A | PART |
|
|
Partial life safety final for phase I (CT#2 Room/Control Room) is complete. There is a sync issue with the project related fire alarm permit that will need to be addressed prior to a final sign off.
Please call Ami when on site. Phone #: ###-#### Inspection requested via web by Ami Tracy
|
FIR18-00258
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 9:44:28 AM | A | PART |
|
|
Phase one (CT#2 Room/Control Room) fire alarm work is complete except there is a audible sync issue and it appears that a visual sync issue. The sync issues will need to be addressed prior to a final sign off.
Brian Phone #: ###-####
|
FIR18-00243
| INSP-Final Inspection | 4/5/2018 | 4/6/2018 | 4/6/2018 9:42:42 AM | A | PART |
|
|
Phase one (CT#2 Room/Control Room) fire sprinkler work is complete.
Please Call Adam With Time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|