Inspections for the day of: Monday, April 6, 2020.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05603 Rough-in4/6/20204/6/20204/6/2020 3:46:01 PMPPASS
3rd floor for cover please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- units 301 302 303 and 304 3rd floor ok to cover
MEC20-00278 Rough-in4/6/20204/6/20204/6/2020 3:45:05 PMPPASS
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- R/I ok excluding pool room and exterior bathroom- Range ducting meets manufactures installation instructions ok to cover
MEC20-00453 Final4/3/20204/6/20204/6/2020 2:55:08 PMPFAIL
re inspection Phone #: ###-#### Inspection requested via web by Randy Hart- still need city approved man j onsite
MEC20-01389 Final4/5/20204/6/20204/6/2020 2:32:33 PMPPASS
Please call Paul prior to arrival to ensure ready for inspection. ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- furnace a/c coil co locking caps ok- virtual video with Josh for inspection
MEC20-01091 Final3/31/20204/6/20204/6/2020 1:41:36 PMPCANC
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- this RTU is for wrong address- need to pull new permit for work on 7709 overland for this RTU permit- this will also need to have a smoke detector test completed by fire crew to final out permit- i went ahead and did inspection while there- please schedule so i can forward this on to fire guys- talked with Dustin about this by phone
MEC20-01343 Conference4/6/20204/6/20204/6/2020 12:46:35 PMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wrong address- need to attach mech permit to right bld and address- reschedule conference
MEC20-01276 Final4/6/20204/6/20204/6/2020 12:22:33 PMPCANC
Journeyman: Chuck ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- can not do inspection til bld permit is issued and city approved drawings onsite-
MEC20-00340 Final4/3/20204/6/20204/6/2020 10:05:56 AMAPART
Francisco is the contact. Air balance will be emailed to you. Phone #: ###-#### Inspection requested via web by stan lillquist- need trap installed on RTU not sure whos doing this- rest is good- temp occupancy
MEC20-00124 Final4/3/20204/6/20204/6/2020 10:05:08 AMAPART
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- gas line needs painted- need to install trap on RTU- rest is good- temp occupancy ok
MEC20-00454 Final4/2/20204/6/20204/6/2020 9:40:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart- need air balance report onsite- need doors installed on furnace closet
MEC18-03615 Mec-Aging Inspection4/6/20204/6/20204/6/2020 9:06:03 AM CANC
called homerowner and left message for him to call me about aging permit
MEC20-01147 Rough-in4/4/20204/6/20204/6/2020 8:50:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Rubin Chervak- R/I ok
MEC20-01148 Rough-in4/4/20204/6/20204/6/2020 8:50:31 AMAPASS
Phone #: ###-#### Inspection requested via web by Rubin Chervak- R/I ok
MEC20-01390 Final4/6/20204/6/20204/6/2020 8:49:29 AMPCANC
INSTALLER DAVID ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt