Inspections for the day of: Monday, April 6, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00186 INSP-Sprinkler Rough-in4/6/20204/6/20204/6/2020 4:03:41 PMPFAIL
Installation does not match plans. Two heads have been piped from the same 1" outlet. Install per plans or provide calculations proving the two heads work as discussed.

Please call Barry when you are on your way. Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00489 INSP-Final Inspection4/6/20204/6/20204/6/2020 2:44:46 PMPPART
Forward flush passed. The interconnection with the fire alarm system was not ready for inspection.

Todd Ketterling is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00186 INSP-Sprinkler Rough-in4/3/20204/6/20204/6/2020 8:54:28 AMAFAIL
I let jim know I was on the way. Waited at the project site 25 minutes and then left. Inspection will need to be rescheduled.
Phone #: ###-#### Inspection requested via web by Connie Danes
FIR20-00236 INSP-Final Inspection4/3/20204/6/20204/6/2020 8:21:18 AMAFAIL
No testing reports and the fire alarm system is not ready for testing.

Please Call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR20-00139 INSP-Final Inspection4/3/20204/6/20204/6/2020 8:20:35 AMAFAIL
No inspection test reports, flow switches and tampers are unhooked and when hooked back up there is a trouble signal also missing a resistor. No testing done. Inspection stopped.

cleared // Buck Phone #: ###-####