Inspections for the day of: Monday, April 6, 2020.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05122 Final4/3/20204/6/20204/6/2020 3:54:04 PMPPASS
chris Phone #: ###-#### Inspection requested via web by Aaron Alandt
- final ok
MEC20-01299 Rough-in4/6/20204/6/20204/6/2020 3:21:58 PMPFAIL
Bj 2085730755. Fireplace as well please Inspection requested via web by william kerwin
- 60lb gas fail
- all ducts in attic need insulated
- need fireplace instructions
- fireplace venting needs insulation shields installed
- gas line penetration needs protective coating
MEC20-01299 Pressure Test4/6/20204/6/20204/6/2020 3:20:19 PMPFAIL
Bj 2085730755. Fireplace as well please Inspection requested via web by william kerwin
- 5lb ok
-60lb gas fail
MEC20-01184 Final4/6/20204/6/20204/6/2020 3:19:42 PMPCANC
Please call at least 30 min prior. Sean will be completing inspection over Zoom app and he needs time to go over there when you are ready. ###-#### Phone #: ###-#### Inspection requested via web by Dan McFate
- no access for video inspection
MEC20-01391 Rough-in4/6/20204/6/20204/6/2020 2:45:31 PMPPASS
Scott ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- R/I ok
MEC20-01349 Pressure Test4/1/20204/6/20204/6/2020 2:08:23 PMPPASS
INSTALLER JAMES ###-####
BUILDING F - UNITS 1928, 1926, 1924, 1922 Phone #: ###-#### Inspection requested via web by Aaron Alandt
4- 20lb gas ok
MEC20-01114 Final4/6/20204/6/20204/6/2020 1:36:58 PMPFAIL
Bj 2085730755. Electrical pernit has been pulled Inspection requested via web by william kerwin
- no electrical permit has been issued yet
MEC20-01373 Rough-in4/2/20204/6/20204/6/2020 1:21:07 PMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- approved man j
- gas pipe penetration needs 10 mill installed
- need access to furnace
- issue reinspection fee
MEC20-01372 Rough-in4/2/20204/6/20204/6/2020 1:20:32 PMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- approved man J
- access to furnace
- issue reinspection fee
MEC20-01371 Rough-in4/2/20204/6/20204/6/2020 1:20:05 PMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- approved man j
- gas pipe penetration needs 10 mill taped installed
-issue reinspection fee
MEC20-01370 Rough-in4/2/20204/6/20204/6/2020 1:18:10 PMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- approved man J
-issue reinspection fee
MEC20-01371 Pressure Test4/2/20204/6/20204/6/2020 1:14:33 PMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 5lb ok
- 20lb ok
- tagged meter location
MEC20-01373 Pressure Test4/2/20204/6/20204/6/2020 1:13:06 PMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb ok
- tagged meter location
MEC20-01372 Pressure Test4/2/20204/6/20204/6/2020 1:10:06 PMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
-20lb ok
- tagged meter location
MEC20-01370 Pressure Test4/2/20204/6/20204/6/2020 12:12:51 PMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 5lb ok
- 20lb ok
- tagged meter location
MIS20-00102 MEC-Final4/3/20204/6/20204/6/2020 11:07:25 AMAFAIL
Inspection for Occupancy: Applicant has been screened w/ Covid-19 questions. Phone #: ###-####
- all appliances on catsers need approved gas flex connetcors installed
- all movable appliances need restraints installed
- any appliances not being used need removed
- any gas line stubs not being used need capped off
- gas line on cook line needs supported
- combustion air for tankless needs re connected
MEC20-01305 Rough-in4/3/20204/6/20204/6/2020 10:10:01 AMAFAIL
Access Code is 9860. Please contact Brian Eddin''s with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Josh Bennett
- see corrections from last inspection
- ok to repair duct insulation where needed
MEC20-01382 Final4/3/20204/6/20204/6/2020 9:58:58 AMAFAIL
Please contact Brian Eddins at ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Josh Bennett
- no access to inspection location and no contact with Brian. Will need to contact with contractor for inspection. Live video chat will be excepted for scope of work being done.
MEC20-01293 Rough-in4/2/20204/6/20204/6/2020 8:31:42 AMACANC
Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
MEC19-04094 Mec-Aging Inspection4/6/20204/6/20204/6/2020 8:27:36 AM PASS
Doc Permit Finaled ok
MEC19-04094 DOC - Permit Finaled4/6/20204/6/20204/6/2020 8:27:17 AMAPASS
Doc Permit Finaled ok