BLD03-00068
| FIRE-Final Inspection | 4/4/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | A | PASS |
|
|
RICHARD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR01-00462
| INSP-Sprinkler Rough-in | 4/4/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | A | PART |
|
|
###-#### okay to cover bathroom in basement; will need heads in switchgear room 4/7/2003 10:31:28 AM
|
BLD01-01347
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/7/2003 at 6:48:05 AM. Contact: ###-####. need detectors at all smoke/fire dampers; all rated doors not installed as shown on plans; audible not loud enough; need to relocate detectors within 5 ft of door with hold opens 4/7/2003 4:33:16 PM
|
FIR01-00573
| INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | NR |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Darla Downs not ready for inspection 4/7/2003 4:25:49 PM
|
FIR02-00326
| INSP-Alarm Testing | 4/4/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Would like inspection at 1pm if possible, if not please let us know when you will be available. ; Phone #: ###-#### Internet Inspection Request from: Rick Groom
|