Inspections for the day of: Monday, April 7, 2003.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00049 INSP-Alarm Testing4/3/20034/7/20034/7/2003 12:00:00 AMAFAIL
###-####. Provide 18ah batteries in FACP. Provide 12 ah batteries in the NAC. Provide map. Duct smoke detectors do not shut down hvac. Provide knox box. a/v's overspaced in the vehicle licence. This one FACP monitors two sprinkler systems in two different addressed buildings 4/7/2003 10:47:38 AM
FIR02-00478 INSP-Alarm Testing4/4/20034/7/20034/7/2003 12:00:00 AMPPART
elevator recall is ok 4/7/2003 3:46:22 PM
BLD02-02287 FIRE-Final Inspection4/4/20034/7/20034/7/2003 12:00:00 AMPPART
DALE; Phone #: ###-#### A temporary occupancy was given until the fire alarm system and the fire sprinkler system is finaled.
One exit sign needs the battery replaced and another needs to be relocated 4/7/2003 3:30:08 PM
FIR02-00423 INSP-Sprinkler Rough-in/Hydro4/7/20034/7/20034/7/2003 12:00:00 AMPPART
See on site approved plans for locations to add upright heads and eq bracing. Other areas still need rough-in inspection 4/7/2003 12:15:41 PM
FIR02-00372 INSP-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPCANC
Troy, This is Patricks cell.
Thanks Have a good day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley TROY CALLED TO HAVE ME CANC THIS INSPECTION AND TO PUT IT IN FOR 4-8-03 AM
MIS02-00240 FIR-Final4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 11:13:55 AM
BLD02-01633 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:02 PM
BLD02-01634 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:18 PM
BLD02-01635 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:27 PM
BLD02-01637 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:36 PM
BLD02-01638 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:44 PM
BLD02-01639 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:42:55 PM
BLD02-01640 FIRE-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPASS
Fire life safety finaled 4/7/2003 3:43:04 PM
FIR02-00476 INSP-Conference4/7/20034/7/20034/7/2003 12:00:00 AMPDONE
I issued a citation to Peak Electric for the installation of fire alarm devices with out approved drawings. The citation number is F000382. The citation was made out to Peak Electric and was signed for by the secretary. I can now sign a temporary occupancy per Dave Millers permission.
FIR02-00476 INSP-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPART
The fie alarm was given temp with dave millers permission until it is installed and tested
FIR02-00473 INSP-Final Inspection4/7/20034/7/20034/7/2003 12:00:00 AMPPART
Fire sprinklers given temp with dave millers permission. There is still some work in the lobby and a restroom that needs to be added near the lobby