FIR03-00049
| INSP-Alarm Testing | 4/3/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | A | FAIL |
|
|
###-####. Provide 18ah batteries in FACP. Provide 12 ah batteries in the NAC. Provide map. Duct smoke detectors do not shut down hvac. Provide knox box. a/v's overspaced in the vehicle licence. This one FACP monitors two sprinkler systems in two different addressed buildings 4/7/2003 10:47:38 AM
|
FIR02-00478
| INSP-Alarm Testing | 4/4/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PART |
|
|
elevator recall is ok 4/7/2003 3:46:22 PM
|
BLD02-02287
| FIRE-Final Inspection | 4/4/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PART |
|
|
DALE; Phone #: ###-#### A temporary occupancy was given until the fire alarm system and the fire sprinkler system is finaled.
One exit sign needs the battery replaced and another needs to be relocated 4/7/2003 3:30:08 PM
|
FIR02-00423
| INSP-Sprinkler Rough-in/Hydro | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PART |
|
|
See on site approved plans for locations to add upright heads and eq bracing. Other areas still need rough-in inspection 4/7/2003 12:15:41 PM
|
FIR02-00372
| INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | CANC |
|
|
Troy, This is Patricks cell.
Thanks Have a good day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley TROY CALLED TO HAVE ME CANC THIS INSPECTION AND TO PUT IT IN FOR 4-8-03 AM
|
MIS02-00240
| FIR-Final | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 11:13:55 AM
|
BLD02-01633
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:02 PM
|
BLD02-01634
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:18 PM
|
BLD02-01635
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:27 PM
|
BLD02-01637
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:36 PM
|
BLD02-01638
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:44 PM
|
BLD02-01639
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:42:55 PM
|
BLD02-01640
| FIRE-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 4/7/2003 3:43:04 PM
|
FIR02-00476
| INSP-Conference | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | DONE |
|
|
I issued a citation to Peak Electric for the installation of fire alarm devices with out approved drawings. The citation number is F000382. The citation was made out to Peak Electric and was signed for by the secretary. I can now sign a temporary occupancy per Dave Millers permission.
|
FIR02-00476
| INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PART |
|
|
The fie alarm was given temp with dave millers permission until it is installed and tested
|
FIR02-00473
| INSP-Final Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 12:00:00 AM | P | PART |
|
|
Fire sprinklers given temp with dave millers permission. There is still some work in the lobby and a restroom that needs to be added near the lobby
|