ELE05-00926
| Electrical Rough-In | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | PASS |
|
|
hallway walls and 2 baths ok to cover 4/7/2005 9:28:25 AM
|
ELE05-00700
| Final | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn called left message to fix sheetrock at washer, and to re-fuse a/c to agree with breaker(40 A), not 60 A. 4/7/2005 10:06:21 AM
|
ELE05-01153
| Temporary Service | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | PASS |
|
|
###-#### - allen t/s u/g n ok 4/7/2005 8:43:59 AM
|
ELE04-03569
| Final | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | PASS |
|
|
rex; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 4/7/2005 8:21:24 AM
|
ELE05-00734
| Final | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 4/6/2005 at 3:30:12 PM. Contact: ###-####. called for access and elect said this was for tomorrow, not today. 4/7/2005 7:35:17 AM
|
ELE05-01133
| Temporary Service | 4/5/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g n ok 4/7/2005 9:58:29 AM
|
ELE05-01145
| Permanent Service | 4/6/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | P | PASS |
|
|
kelly ###-#### p/s o/h to exst meter ok. left message to backfill before call for power. 4/7/2005 12:36:12 PM
|
ELE05-01157
| Electrical Rough-In | 4/7/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | P | FAIL |
|
|
###-#### - larry called contr, left corr notice, 300.4(A)(1)&(D) nailplates and 1 1/4" shall be done as code states,BCC all make-up shall be done and boxes installed, 250.64(D) grounding electrode conductor tap shall be made outside of enclosure, 110.14(D) grounds shall be spliced with devices identified for the purpose, 314.16 boxes shall not exceed fill as calculated, 210.52 recpts shall be installed by fireplace if cabinets or cupboards in wall 4/7/2005 4:59:28 PM
|
ELE05-01166
| Final | 4/7/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | P | PASS |
|
|
###-#### - leon Note: check air conditioners ok to final 4/7/2005 4:37:36 PM
|
ELE05-01168
| Final | 4/7/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | P | PASS |
|
|
Contact Darrick, ###-####.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final 4/7/2005 3:46:01 PM
|
ELE05-01165
| Final | 4/7/2005 | 4/7/2005 | 4/7/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s u/g exst ok chgd meter base 4/7/2005 1:35:13 PM
|