FIR06-00149
| INSP-Sprinkler Rough-in | 4/6/2006 | 4/7/2006 | 4/7/2006 5:38:53 PM | P | FAIL |
|
|
Approved plans not available for verification of field installation, no contractor on site at the time of inspection.
|
FIR05-00564
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 5:36:28 PM | A | FAIL |
|
|
The required plans reflecting field changes were not made available on site for review.
|
FIR05-00426
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 5:33:16 PM | A | PASS |
|
|
Corrections have been verified, alarm permit finaled.
|
FIR04-00313
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 3:26:12 PM | P | DEFR |
|
|
If possible can test be conducted at 2:30 or later so kitchen service will not be interrupted? Someone with knowledge of fire alarm panel will also need to be present.; Phone #: ###-#### Internet Inspection Request from: Michael Heath No time available to perform this inspection today, to be rescheduled per conversation with contractor.
|
FIR06-00193
| INSP-Final Inspection | 4/5/2006 | 4/7/2006 | 4/7/2006 3:23:07 PM | P | PASS |
|
|
Overhead sprinkler work is satisfactory, spare heads of the type installed added to head box while on site, inspection passed.
|
FIR05-00712
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 3:21:35 PM | P | PART |
|
|
Re-tested items from previous correction notices on third, second and first floors, tested guest rooms on ground level, elevator devices tested okay however the second floor elevator fire door fails to close due to improper door adjustment, notification and detection devices in the common corridor ground level tested okay, still need to test and verify items on pending resubmitted plans including added SD's, co detectors, changed nac locations, added horns, and mag locks at egress doors, also provide updated map at the panel.
|
FIR06-00123
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 12:34:11 PM | A | PART |
|
|
Fire sprinkler work appears satisfactory, however the approved stamped plans, permit, review notes, and inspection card were not available on site at the time of inspection, also need to provide spare heads of the type installed in the head box.
|
FIR05-00449
| INSP-Alarm Testing | 4/6/2006 | 4/7/2006 | 4/7/2006 12:31:10 PM | A | FAIL |
|
|
Two pull station addresses on the ground level are switched (#41 and 42), need to relocate one SD min. 3' away from HVAC supply diffuser in the corridor, audibility has been adjusted to the appropriate level in the mech. mezz as required, tested notification and detection devices on the ground level, 8 SD above the lobby not tested at this time due to access issues.
|
BLD05-03007
| FIRE-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 12:25:13 PM | A | PART |
|
|
Life safety is acceptable, final pending shell project related alarm and sprinkler permit finals. Temporary occupancy granted per D. Hanneman.
|
BLD05-02976
| FIRE-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 12:23:15 PM | A | PART |
|
|
Life safety is acceptable, final pending shell project related alarm and sprinkler finals. Temporary occupancy granted per D Hanneman.
|
FIR05-00804
| INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 9:09:07 AM | A | CANC |
|
|
Forrest, This is ready again. Fire alarms guys used UVIR tester. Please call when you think you can be here. Thanks, Harry; Phone #: ###-#### Internet Inspection Request from: Harry Thompson Inspection cancelled from web by: Harry Thompson
|