ESC08-00945
| General Inspection | 4/7/2009 | 4/7/2009 | 4/7/2009 3:13:50 PM | P | PASS |
|
|
site ok
|
ELE09-00564
| Temporary Service | 4/6/2009 | 4/7/2009 | 4/7/2009 3:12:44 PM | P | FAIL |
|
|
Internet Inspection Request from: Rowdy Monroe called corr. 200.2 (B) shall terminate GEC at neutral bus
|
ESC09-00096
| General Inspection | 4/7/2009 | 4/7/2009 | 4/7/2009 3:09:11 PM | P | PART |
|
|
card posted excavation work being done at time of inspection site ok
|
ELE09-00565
| Temporary Service | 4/6/2009 | 4/7/2009 | 4/7/2009 3:07:40 PM | P | PASS |
|
|
Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
|
ELE09-00570
| Permanent Service | 4/7/2009 | 4/7/2009 | 4/7/2009 2:17:56 PM | P | PASS |
|
|
there are 3 meters out there, need 52457281S inspected//please call David ###-#### p/s o/h rec. ok
|
ELE09-00570
| Final | 4/7/2009 | 4/7/2009 | 4/7/2009 2:17:36 PM | P | PASS |
|
|
there are 3 meters out there, need 52457281S inspected//please call David ###-####
|
ESC08-00179
| General Inspection | 4/7/2009 | 4/7/2009 | 4/7/2009 1:34:48 PM | P | PART |
|
|
some excavation work going on some dirt on hard surfaces at this time
|
ELE08-02167
| Electrical Rough-In | 4/7/2009 | 4/7/2009 | 4/7/2009 1:32:54 PM | P | FAIL |
|
|
Ceiling Phone #: ###-#### correction met contr 300.4(E) shall provide 11/2" or RMC, IMC for conduit at roof decking
|
ELE09-00558
| Electrical Rough-In | 4/7/2009 | 4/7/2009 | 4/7/2009 12:38:42 PM | P | PART |
|
|
Eric- trench Phone #: ###-#### u/g middle section of parking lot ok could not respond to ESC permit said it has wrong status
|
ELE09-00014
| ELE-Aging Inspection | 4/7/2009 | 4/7/2009 | 4/7/2009 11:14:46 AM | | DONE |
|
|
|
ELE09-00014
| Final | 4/7/2009 | 4/7/2009 | 4/7/2009 11:14:19 AM | A | PASS |
|
|
|
ELE09-00014
| Electrical Rough-In | 4/7/2009 | 4/7/2009 | 4/7/2009 11:11:42 AM | A | PASS |
|
|
ok conduit was installed by elect contr last year
|
ESC08-00765
| Random Inspection | 4/7/2009 | 4/7/2009 | 4/7/2009 9:02:21 AM | A | PART |
|
|
site ok
|
ELE09-00561
| Rough-In Permanent Service | 4/6/2009 | 4/7/2009 | 4/7/2009 9:01:16 AM | A | PASS |
|
|
Please provide rough-in permanent service inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean p/s u/g new space#2 ok
|
ELE09-00560
| Rough-In Permanent Service | 4/6/2009 | 4/7/2009 | 4/7/2009 9:00:32 AM | A | PASS |
|
|
Please provide rough-in permanent service inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean p/s u/g new space #1 ok
|
ELE08-03023
| Rough-In Permanent Service | 4/6/2009 | 4/7/2009 | 4/7/2009 8:58:45 AM | A | PASS |
|
|
Please provide rough-in permanent service inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean p/s u/g new for house meter ok
|