FIR09-00728 INSP-Conference4/6/20104/7/20104/7/2010 3:56:19 PMPDONE
This conference was to discuss the placement of a manual pull station at the center east exit. The request was to place the pull station on a cabinet. That was declined. It was decided that the pull station would be place on the left side door frame, next to the refrigerator. Mounting height was also discussed.
BLD10-00299 FIRE-Final Inspection4/7/20104/7/20104/7/2010 2:46:48 PMPPASS
Life safety passed.
FIR10-00141 INSP-Conference4/7/20104/7/20104/7/2010 2:45:14 PMPDONE
I spoke to Tim Frost and he and the code are ok with the area that was previously shown to be a sprinklered storage room now being a unsprinklered exterior patio.
FIR10-00143 INSP-Sprinkler Rough-in4/6/20104/7/20104/7/2010 10:43:16 AMAPASS
Work is complete. Piping can be covered.
BLD10-00649 FIRE-Final Inspection4/6/20104/7/20104/7/2010 10:16:13 AMAPASS
Life safety passed.
FIR05-00077 INSP-Final Inspection4/6/20104/7/20104/7/2010 9:49:10 AMAPASS
Inspection was performed by Mary.
FIR10-00073 INSP-Sprinkler Rough-in4/6/20104/7/20104/7/2010 9:42:07 AMAFAIL
This inspectio was for phase 1. All items tested ok except for the duct detector located in the main existing exit corridor did not shut down the hvac unit when activated.
FIR10-00141 INSP-Sprinkler Rough-in4/6/20104/7/20104/7/2010 9:41:00 AMAPASS
The overspaced sprinkler pendants have been corrected. Sprinkler piping is ok to cover.
FIR10-00131 INSP-Sprinkler Rough-in4/6/20104/7/20104/7/2010 9:39:41 AMAPASS
Sprinkler piping is ok to cover.
BLD10-00299 FIRE-Final Inspection4/6/20104/7/20104/7/2010 9:12:34 AMAFAIL
All items have been corrected except the emergency lights do not switch to battery backup as required. The owner has been turning off the lighting circuit at the breaker panel thus depleting the batteries every night.