ELE14-00830
| Final | 4/4/2014 | 4/7/2014 | 4/8/2014 10:07:12 AM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER called contractor, told to change handi-box splice box to weather proof type, behind unit on wall
|
ELE14-00836
| Electrical Rough-In | 4/7/2014 | 4/7/2014 | 4/7/2014 2:55:48 PM | P | PASS |
|
|
Access to project at back of house Phone #: ###-#### >> Inspection requested via web by Brad Girard ri ok
|
ELE14-00828
| Temporary Service | 4/4/2014 | 4/7/2014 | 4/7/2014 2:33:22 PM | P | PASS |
|
|
Mucho Phone #: ###-#### t/s u/g n ok
|
ELE14-00840
| Electrical Rough-In | 4/7/2014 | 4/7/2014 | 4/7/2014 1:41:55 PM | P | PASS |
|
|
Need Rough in inspection for outside soffits. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok cover soffits only
|
ELE14-00267
| Electrical Rough-In | 4/7/2014 | 4/7/2014 | 4/7/2014 1:00:34 PM | P | PASS |
|
|
Ceiling inspection in Fitness area. Phone #: ###-#### >> Inspection requested via web by Steve McCloy ok cover fitness ceiling only
|
ELE14-00830
| Electrical Rough-In | 4/4/2014 | 4/7/2014 | 4/7/2014 10:36:06 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER ri ok
|
ELE14-00787
| Electrical Rough-In | 4/4/2014 | 4/7/2014 | 4/7/2014 10:32:30 AM | A | PASS |
|
|
Contact: Brian Gee please call 30 minutes before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden ri baths charging area, halls, ok
|
ELE14-00709
| Final | 4/6/2014 | 4/7/2014 | 4/7/2014 9:53:55 AM | A | FAIL |
|
|
Potting and underground Phone #: ###-#### >> Inspection requested via web by Louis Keller called, left message, left correction notice, NEC 680.10 u/g raceways shall be minimum 18" deep, 310.15(B)2(b) shall maintain conduit spacing, 350.26 there shall not be more than 360 degree total bends
|
ELE14-00685
| Rough-In Permanent Service | 4/4/2014 | 4/7/2014 | 4/7/2014 9:17:20 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE14-00577
| Permanent Service | 4/7/2014 | 4/7/2014 | 4/7/2014 8:44:15 AM | A | FAIL |
|
|
Jon Phone #: ###-#### >> Inspection requested via web by Sean DeLacy met electrician, told shall drive in ground rods and provide bond bushings per NEC 250, shall mount meter base then recall
|
ELE14-00577
| Electrical Rough-In | 4/7/2014 | 4/7/2014 | 4/7/2014 6:33:43 AM | A | CANC |
|
|
Jon. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|