Inspections for the day of: Monday, April 7, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00830 Final4/4/20144/7/20144/8/2014 10:07:12 AMANR
Phone #: ###-#### >> Inspection requested via web by PAT MILLER called contractor, told to change handi-box splice box to weather proof type, behind unit on wall
ELE14-00836 Electrical Rough-In4/7/20144/7/20144/7/2014 2:55:48 PMPPASS
Access to project at back of house Phone #: ###-#### >> Inspection requested via web by Brad Girard ri ok
ELE14-00828 Temporary Service4/4/20144/7/20144/7/2014 2:33:22 PMPPASS
Mucho Phone #: ###-#### t/s u/g n ok
ELE14-00840 Electrical Rough-In4/7/20144/7/20144/7/2014 1:41:55 PMPPASS
Need Rough in inspection for outside soffits. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok cover soffits only
ELE14-00267 Electrical Rough-In4/7/20144/7/20144/7/2014 1:00:34 PMPPASS
Ceiling inspection in Fitness area. Phone #: ###-#### >> Inspection requested via web by Steve McCloy ok cover fitness ceiling only
ELE14-00830 Electrical Rough-In4/4/20144/7/20144/7/2014 10:36:06 AMAPASS
Phone #: ###-#### >> Inspection requested via web by PAT MILLER ri ok
ELE14-00787 Electrical Rough-In4/4/20144/7/20144/7/2014 10:32:30 AMAPASS
Contact: Brian Gee please call 30 minutes before going Phone #: ###-#### >> Inspection requested via web by Deb Gooden ri baths charging area, halls, ok
ELE14-00709 Final4/6/20144/7/20144/7/2014 9:53:55 AMAFAIL
Potting and underground Phone #: ###-#### >> Inspection requested via web by Louis Keller called, left message, left correction notice, NEC 680.10 u/g raceways shall be minimum 18" deep, 310.15(B)2(b) shall maintain conduit spacing, 350.26 there shall not be more than 360 degree total bends
ELE14-00685 Rough-In Permanent Service4/4/20144/7/20144/7/2014 9:17:20 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE14-00577 Permanent Service4/7/20144/7/20144/7/2014 8:44:15 AMAFAIL
Jon Phone #: ###-#### >> Inspection requested via web by Sean DeLacy met electrician, told shall drive in ground rods and provide bond bushings per NEC 250, shall mount meter base then recall
ELE14-00577 Electrical Rough-In4/7/20144/7/20144/7/2014 6:33:43 AMACANC
Jon. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy