Inspections for the day of: Tuesday, April 7, 2015.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTim Frost
TitleFIRE PLANS EXAMINER
Phone #208-608-7110
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF14-00028 INSP-Supply line flush4/6/20154/7/20154/8/2015 12:00:00 AMAPASS
Passed flush
FIR15-00096 INSP-Sprinkler Rough-in4/6/20154/7/20154/7/2015 12:00:00 AMAPEND
Inspected all of second floor except for east wing which was inspected by Troy Cobbley. Second floor has passed rough in. Did not inspect the corridors.
______________
Apparently, there has been a change in the design. The drywall is not going to the deck. This leaves the entire space between the second floor ceiling and the third floor an open combustible concealed space. This space will require fire protection. Until this matter has been resolved the cover on the second floor is on hold.