BLD16-00850
| FIRE-Final Inspection | 4/6/2016 | 4/7/2016 | 4/7/2016 2:32:19 PM | A | FAIL |
|
|
Exit signs and emergency lights are not repaired yet.
|
FIR16-00145
| INSP-Sprinkler Rough-in/Hydro | 4/7/2016 | 4/7/2016 | 4/7/2016 1:40:50 PM | P | PASS |
|
|
The new piping has been tied into the existing system. Hydro static test a city pressure passed. Tim is ok with the 8" lateral siesmic bracing connecting to the bottom chord of the girder. Need alarm interconnects and forward flush for final.
|
BLD16-00922
| FIRE-Final Inspection | 4/6/2016 | 4/7/2016 | 4/7/2016 10:57:13 AM | A | FAIL |
|
|
Resubmit to plan reivew for approval of Retail Display and provide annual inspection for the basement fire sprinkler system
|
FIR16-00228
| INSP-Final Inspection | 4/6/2016 | 4/7/2016 | 4/7/2016 10:51:42 AM | A | PASS |
|
|
Permit finaled
|