Inspections for the day of: Tuesday, April 7, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01227 Final4/7/20204/7/20204/7/2020 1:49:35 PMPPASS
Questions please call Eric at ###-#### Phone #: ###-#### Inspection requested via web by Bonnie Page
Final ok
ELE20-01227 Permanent Service4/7/20204/7/20204/7/2020 1:48:37 PMPPASS
Questions please call Eric at ###-#### Phone #: ###-#### Inspection requested via web by Bonnie Page
p/s u/g n ok
ELE20-01225 Rough-In Permanent Service4/6/20204/7/20204/7/2020 11:52:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Rough-in ok to cover
p/s u/g n ok
ELE19-04889 Final4/6/20204/7/20204/7/2020 10:55:41 AMAFAIL
Call Efren 1/2 hr prior so he can meet you there Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
210.8 Recetpacles located within 6' of a sink shall have GFCI protection
406 All receptacles located in outdoors shall be WR rated
300 Spark ring required behind combustible material(entry in wood wall)
OCPD exceeds water heater rating at 23 amps 30 installed
ELE19-02491 Final4/6/20204/7/20204/7/2020 10:20:30 AMAPASS
CALL AARON VANCE WITH QUESTIONS.
No plans on site. This sign does not required a building final
under 6'' in height. Phone #: ###-#### Inspection requested via web by Dana Vance
Sign final ok
ELE20-00365 Final4/6/20204/7/20204/7/2020 10:00:45 AMAPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE20-00975 Temporary Service4/6/20204/7/20204/7/2020 9:24:00 AMAPASS
Temp. pole located in back yard, next to new concrete slab Phone #: ###-#### Inspection requested via web by Troy Cobb
t/s o/h n ok