Inspections for the day of: Tuesday, April 8, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04225 ELE-Aging Inspection4/8/20084/8/20084/8/2008 4:27:53 PM DONE
no word on bld as yet, if not required, will final
ELE08-00659 Final4/7/20084/8/20084/8/2008 4:15:00 PMPFAIL
Final Swimming Pool Inspection. Phone #: ###-#### Internet Inspection Request from: Jenni Keller called contractor, NEC 680.(A)(3) shall provide receptacle within 20' of inside pool wall
ELE08-00717 Electrical Rough-In4/8/20084/8/20084/8/2008 3:30:51 PMPPASS
adam Phone #: ###-#### ok to cover upstairs only
ELE08-00841 Conference4/8/20084/8/20084/8/2008 2:46:05 PMPDONE
Andy Phone #: ###-#### Bob, work may be being done with out a building permit, I see a plm permit was pulled for 10 fixtures and Andy said they are up to 6 rooms now for the electrical, Pleasae check this out and stop work if need a bld permit . PS I will put a note in the plm permit also so who ever gets there first can check it out. Thanks Darla met electrician, determined that there needs to be stop work, posted stop work, sent electrician home, called office
ELE08-00840 Rough-In Permanent Service4/8/20084/8/20084/8/2008 1:51:18 PMPFAIL
jeremy-- the n.w. unit Phone #: ###-#### called, left correction notice, NEC 250.52(A)(3) shall provide concrete encased electrode, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC shall provide address, main breaker, wire empty boxes, and provide boxes for mbr bath lights,
ELE08-00827 Electrical Rough-In4/8/20084/8/20084/8/2008 1:07:05 PMPNR
mike Phone #: ###-#### Internet Inspection Request from: Mike Swift called, left message, left correction notice, BCC all make-up shall be done, all boxes shall be installed, all wiring into boxes
ELE08-00642 Permanent Service4/8/20084/8/20084/8/2008 12:13:16 PMPPASS
pat Phone #: ###-#### p/s o/h rec ok
ELE08-00642 Rough-In Permanent Service4/7/20084/8/20084/8/2008 10:19:40 AMACANC
pat - please call prior to inspection Phone #: ###-#### see conference
ELE08-00812 Electrical Rough-In4/8/20084/8/20084/8/2008 9:46:36 AMPPART
bryan Phone #: ###-#### looked at part of u/g for aisle kiosks, west end,1st floor
ELE08-00642 Conference4/8/20084/8/20084/8/2008 9:43:17 AMADONE
pat - please call prior to inspection Phone #: ###-#### met contractor, talked about mast and grounding, 4-wire to dryer
ELE07-03975 Conference4/7/20084/8/20084/8/2008 9:14:53 AMADONE
joe Phone #: ###-#### looked at possibilities for new service for existing building and new addition - locations, layouts, room remodel, phone board remodel. Reviewed fire alarm circuits ahead of main at other facility.
ELE08-00625 Electrical Rough-In4/7/20084/8/20084/8/2008 8:11:52 AMAPASS
ceiling inspection Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin contractor will change unit address, ok to cover ceiling only