Inspections for the day of: Wednesday, April 8, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00018 INSP-Sprinkler Rough-in/Hydro4/7/20094/8/20094/8/2009 5:29:16 PMAFAIL
See latest approved plan set red lines for areas on the 1st and 2nd floors in need of correction.
FIR08-00018 INSP-Final Inspection4/7/20094/8/20094/8/2009 5:27:29 PMPNR
Scheduled by a contractor via Hello! on 4/7/2009 at 8:30:28 AM. Contact: ###-####.
BLD08-01848 FIRE-Conference4/8/20094/8/20094/8/2009 5:27:12 PMPDONE
Regarding site fire alarm work inspection schedule.
FIR09-00101 INSP-Sprinkler Rough-in/Hydro4/7/20094/8/20094/8/2009 5:22:54 PMPPART
Overhead changes per the scope of work indicated are approved for cover at the drop ceilings.
FIR08-00737 INSP-Sprinkler Rough-in/Hydro4/7/20094/8/20094/8/2009 12:26:05 PMAPART
Concluded satisfactory 24 hour air test for the new dry system.
FIR08-00838 FIR-Aging Inspection4/8/20094/8/20094/8/2009 12:24:31 PM DONE
Work in progress, construction underway.
BLD08-02536 FIRE-Final Inspection4/7/20094/8/20094/8/2009 12:10:21 PMAPASS
Project related fire alarm and sprinkler permits finaled, correction notice list issued 2/20 is done, inspection passed.
BLD08-02535 FIRE-Final Inspection4/7/20094/8/20094/8/2009 12:07:22 PMAPASS
C/N items per last inspection 2/20 are finished, fire life safety for the vanilla shell okayed.
FIR09-00068 INSP-Final Inspection4/7/20094/8/20094/8/2009 12:05:05 PMAFAIL
Need to install a WP notification appliance as per approved plans in the beer cooler, HS at the refrigeration equipment mechanical room is obstructed, missing coverage at the deli counter food preparation room, coverage between ceiling mount 115cd strobes at the sales floor between ceiling elevation changes/obstruction to be verified during functional test.
BLD09-00405 FIRE-Final Inspection4/7/20094/8/20094/8/2009 11:58:10 AMAPASS
Correction notice items verified for completion.