ELE11-01094
| ELE-Aging Inspection | 4/8/2013 | 4/8/2013 | 4/9/2013 2:17:30 PM | | DONE |
|
|
still under construction
|
ELE13-00830
| Permanent Service | 4/6/2013 | 4/8/2013 | 4/8/2013 2:29:04 PM | P | PASS |
|
|
This is a service change. Please try to give us until 1:00 to get it ready for inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h rec ok
|
ELE13-00584
| Final | 4/8/2013 | 4/8/2013 | 4/8/2013 2:11:20 PM | P | PASS |
|
|
Fire pump inspection for ID Power turn on. Phone #: ###-#### >> Inspection requested via web by Kendra Lanham final ok
|
ELE13-00584
| Permanent Service | 4/8/2013 | 4/8/2013 | 4/8/2013 2:08:25 PM | P | PASS |
|
|
p/s u/g rec ok
|
ELE13-00835
| Final | 4/8/2013 | 4/8/2013 | 4/8/2013 1:00:13 PM | P | FAIL |
|
|
Please call Jeff if you have any questions or if the house is locked. Thanks Phone #: ###-#### >> Inspection requested via web by Brandon Blackham NEC 250.53(G) The electrode shall be installed at least 8ft. incontact with the soil. NEC 250.56 A single electrode consisting of rod,pipe or plate that does not have a resistance to ground of 25 ohms or less to ground shall be augmented by one additional electrode. Inspection should be schedule as an permanent service so Idaho power will respond
|
ELE13-00815
| Rough-In Permanent Service | 4/8/2013 | 4/8/2013 | 4/8/2013 12:12:08 PM | P | PASS |
|
|
Heedo Phone #: ###-#### rough-in p/s u/g n ok
|
ELE12-00329
| Final | 4/8/2013 | 4/8/2013 | 4/8/2013 9:41:00 AM | P | PASS |
|
|
Ultra beauty wall sign UL listed final ok
|
GCE12-00191
| GCE-Final | 4/5/2013 | 4/8/2013 | 4/8/2013 9:10:11 AM | A | PASS |
|
|
Permit for Perm. Service only - passed 4/1 final ok
|
ELE13-00263
| Electrical Rough-In | 4/6/2013 | 4/8/2013 | 4/8/2013 8:51:22 AM | A | PASS |
|
|
Soffit in lobby and 4 pony walls for nurse station Phone #: ###-#### >> Inspection requested via web by Patrick D Gill rough-in ok cover soffits in lobby and 2 pony walls on east side
|
ELE13-00616
| Electrical Rough-In | 4/5/2013 | 4/8/2013 | 4/8/2013 8:39:14 AM | A | PASS |
|
|
mike Phone #: ###-#### rough-in ok cover hard lid
|
ELE13-00824
| Permanent Service | 4/5/2013 | 4/8/2013 | 4/8/2013 8:17:38 AM | A | PASS |
|
|
Need inspection for existing service because it was turned off for more than one year. Lock box on gas meter on North side of garage. Code 4907 Phone #: ###-#### >> Inspection requested via web by Alan Lusk p/s u/g rec ok
|
ELE12-02764
| Electrical Rough-In | 4/5/2013 | 4/8/2013 | 4/8/2013 12:00:00 AM | P | CANC |
|
|
ERIC Phone #: ###-####//cancelled at 12:45 on 4/8/13
|