BLD12-01914
| FIRE-Conference | 4/8/2014 | 4/8/2014 | 4/9/2014 2:19:04 PM | P | DONE |
|
|
Spoke about fire/smoke dampers and door hardware.
|
FIR14-00076
| INSP-Sprinkler Rough-in/Hydro | 4/8/2014 | 4/8/2014 | 4/8/2014 3:40:57 PM | P | PASS |
|
|
First and second floor rough-in and overhead hydro passed for the In-Fill
|
FIR13-00697
| INSP-Sprinkler Rough-in | 4/8/2014 | 4/8/2014 | 4/8/2014 3:15:29 PM | P | PASS |
|
|
See the city approved plans for the piping above the lay-in ceilings in the Kitchen area that are ok to cover.
|
BLD14-00775
| FIRE-Final Inspection | 4/7/2014 | 4/8/2014 | 4/8/2014 3:14:42 PM | P | PASS |
|
|
Life safety passed. Repair or remove the two exit signs prior to the building inspection.
|
BLD14-00064
| FIRE-Final Inspection | 4/7/2014 | 4/8/2014 | 4/8/2014 3:13:26 PM | P | FAIL |
|
|
Provide small documents, provide ADA compliant hardware for all doors per note #6, provide fire extinguishers as discussed, demo walls and install new walls as per the plans or get changes ok with plan review, provide building address as discussed.
|
FIR14-00146
| INSP-Final Inspection | 4/7/2014 | 4/8/2014 | 4/8/2014 10:45:57 AM | A | PASS |
|
|
Permit finaled
|