ELE15-00642
| Final | 4/8/2015 | 4/8/2015 | 4/8/2015 2:50:19 PM | P | FAIL |
|
|
Lynn Phone #: ###-#### 314.25 All boxes shall have covers installed. 5- 4sq covers and black conductor hanging out of box with white surface blank installed.
|
ELE15-00897
| Electrical Rough-In | 4/8/2015 | 4/8/2015 | 4/8/2015 2:14:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL Front IT room, and new break room wall rough in ok cover
|
ELE15-00872
| Electrical Rough-In | 4/8/2015 | 4/8/2015 | 4/8/2015 1:33:08 PM | P | PASS |
|
|
PLease Call ###-#### ask for Russell. He can meet you in 5 minutes. Rough in on kitchen remodel. Phone #: ###-#### Inspection requested via web by Randy Fletcher Wire above panel to be in a void above cabinet. Kitchen and mud room rough in ok cover
|
GCE15-00048
| GCE-Final | 4/8/2015 | 4/8/2015 | 4/8/2015 12:46:38 PM | P | PASS |
|
|
Robert ###-#### Final ok
|
ELE13-00731
| ELE-Aging Inspection | 4/8/2015 | 4/8/2015 | 4/8/2015 12:25:38 PM | | DONE |
|
|
Drove by work space has not been improved.
|
ELE13-00662
| Final | 4/8/2015 | 4/8/2015 | 4/8/2015 10:20:45 AM | P | PASS |
|
|
UL listing confirmed. Final ok
|
ELE15-00642
| Final | 4/7/2015 | 4/8/2015 | 4/8/2015 10:11:47 AM | A | NR |
|
|
Lynn Phone #: ###-#### 300.11 Light boxes to support, floor boxes to set on floor surface, 324.25 boxes above grid to cover, 110.3 receptacle outlets not working.
|
ELE15-00633
| Final | 4/6/2015 | 4/8/2015 | 4/8/2015 9:38:38 AM | A | CANC |
|
|
just ceiling. Change to am from pm per Ben from Mountain Power Elect. // Ben Phone #: ###-#### Needed rough in inspection
|
ELE15-00633
| Electrical Rough-In | 4/8/2015 | 4/8/2015 | 4/8/2015 9:31:42 AM | P | PASS |
|
|
just ceiling. Change to am from pm per Ben from Mountain Power Elect. // Ben Phone #: ###-#### Grid rough in ok cover
|
ELE15-00922
| Rough-In Permanent Service | 4/8/2015 | 4/8/2015 | 4/8/2015 9:11:44 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
|
ELE15-00920
| Final | 4/7/2015 | 4/8/2015 | 4/8/2015 8:43:59 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
ELE15-00920
| Permanent Service | 4/8/2015 | 4/8/2015 | 4/8/2015 8:43:24 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan p/s u/g rec ok
|