Inspections for the day of: Wednesday, April 8, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF15-00011 INSP-Final4/7/20154/8/20154/9/2015 4:13:33 PMPPASS
Hood suppression system operated correctly. Gas valve adjusted while on site.
NAF15-00012 INSP-Final4/7/20154/8/20154/9/2015 4:12:03 PMPPASS
Permit ok to final. Per Forrest France
NAF15-00012 INSP-Sprinkler Rough-in/Hydro4/7/20154/8/20154/9/2015 4:11:20 PMPPART
Ok to cover. Per Forrest France.
NAF15-00013 INSP-Final4/7/20154/8/20154/9/2015 4:10:08 PMPPASS
Permit finaled.
NAF15-00001 INSP-Sprinkler Rough-in/Hydro4/7/20154/8/20154/9/2015 4:05:54 PMPNR
Missing siesmic bracing, retaining straps, tie-ins. Riser and aux. drain incomplete at this time. Partial inspection only. Per Forrest France.
NAF15-00001 INSP-Supply line flush4/7/20154/8/20154/9/2015 4:03:42 PMPFAIL
Provide sufficient method to complete flushing per NFPA 13. Inspection completed per Forrest France
NAF14-00020 INSP-Final4/7/20154/8/20154/8/2015 12:00:00 AMAFAIL
Correction items include NAC trouble on circuit two, non-functional a/v on the third floor. Approved plans do not show ADA unit visual appliances. Riser monitoring tested ok. Per Forrest France.