NAF15-00011
| INSP-Final | 4/7/2015 | 4/8/2015 | 4/9/2015 4:13:33 PM | P | PASS |
|
|
Hood suppression system operated correctly. Gas valve adjusted while on site.
|
NAF15-00012
| INSP-Final | 4/7/2015 | 4/8/2015 | 4/9/2015 4:12:03 PM | P | PASS |
|
|
Permit ok to final. Per Forrest France
|
NAF15-00012
| INSP-Sprinkler Rough-in/Hydro | 4/7/2015 | 4/8/2015 | 4/9/2015 4:11:20 PM | P | PART |
|
|
Ok to cover. Per Forrest France.
|
NAF15-00013
| INSP-Final | 4/7/2015 | 4/8/2015 | 4/9/2015 4:10:08 PM | P | PASS |
|
|
Permit finaled.
|
NAF15-00001
| INSP-Sprinkler Rough-in/Hydro | 4/7/2015 | 4/8/2015 | 4/9/2015 4:05:54 PM | P | NR |
|
|
Missing siesmic bracing, retaining straps, tie-ins. Riser and aux. drain incomplete at this time. Partial inspection only. Per Forrest France.
|
NAF15-00001
| INSP-Supply line flush | 4/7/2015 | 4/8/2015 | 4/9/2015 4:03:42 PM | P | FAIL |
|
|
Provide sufficient method to complete flushing per NFPA 13. Inspection completed per Forrest France
|
NAF14-00020
| INSP-Final | 4/7/2015 | 4/8/2015 | 4/8/2015 12:00:00 AM | A | FAIL |
|
|
Correction items include NAC trouble on circuit two, non-functional a/v on the third floor. Approved plans do not show ADA unit visual appliances. Riser monitoring tested ok. Per Forrest France.
|