Inspections for the day of: Friday, April 8, 2016.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01111 Final4/7/20164/8/20164/8/2016 3:25:29 PMPPASS
Please contact Danny with any questions. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
ELE16-01117 Final4/8/20164/8/20164/8/2016 2:47:07 PMPPASS
Replace mast and meter base from fallen tree Phone #: ###-#### Inspection requested via web by Cilnt Pierce
Final ok
ELE16-01117 Permanent Service4/8/20164/8/20164/8/2016 2:45:39 PMPPASS
Replace mast and meter base from fallen tree Phone #: ###-#### Inspection requested via web by Cilnt Pierce
p/s o/h rec ok
ELE16-01066 Final4/8/20164/8/20164/8/2016 2:20:30 PMPPASS
Jim Phone #: ###-#### Benchmark to pull permit for adding light in hall and receptacle on 24" wall in bed. Final ok
ELE16-01114 Temporary Service4/8/20164/8/20164/8/2016 1:30:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01115 Temporary Service4/8/20164/8/20164/8/2016 1:30:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01116 Temporary Service4/8/20164/8/20164/8/2016 1:24:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01112 Temporary Service4/8/20164/8/20164/8/2016 1:23:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01113 Temporary Service4/8/20164/8/20164/8/2016 1:17:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01118 Temporary Service4/8/20164/8/20164/8/2016 1:14:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01111 Temporary Service4/8/20164/8/20164/8/2016 1:13:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01110 Temporary Service4/8/20164/8/20164/8/2016 12:51:21 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-01064 Electrical Rough-In4/7/20164/8/20164/8/2016 12:50:39 PMAPASS
Please call 30min ahead for access - Curtis Phone #: ###-####
Addition adds to 2 bedrooms and closet rough in ok cover
ELE16-01059 Rough-In Permanent Service4/7/20164/8/20164/8/2016 12:13:44 PMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Asked contractor about second 40 amp 240 volt circuit in living room and he did not know. Warned about 2nd range location violation. Will check on final.
Rough in ok cover p/s u/g n ok
ELE16-00747 Electrical Rough-In4/7/20164/8/20164/8/2016 11:37:02 AMAPASS
Wall cover Phone #: ###-#### Inspection requested via web by cris flores
South end of building. Office, mech., storage walls rough in ok cover
ELE16-01099 Electrical Rough-In4/7/20164/8/20164/8/2016 11:18:27 AMAPASS
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
Wall by kitchen rough in ok cover
ELE16-01107 Electrical Rough-In4/7/20164/8/20164/8/2016 11:05:51 AMAPASS
This is an inspection for the pool bonding. Phone #: ###-#### Inspection requested via web by Warren Fry
Pool shell bond to equipment and 4 corners only rough in ok cover
ELE16-01091 Temporary Service4/7/20164/8/20164/8/2016 10:30:27 AMANR
Power off for more than 1 year Phone #: ###-#### Inspection requested via web by Cilnt Pierce
Service reconnected under permit ELE16-00188. Spoke to contractor they will remove all wires from breakers not needed and use GFCI protected circuits for temp power and recall.
ELE16-01102 Temporary Service4/7/20164/8/20164/8/2016 9:35:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.53- Grounding electrode conductor shall be connected to grounding electrode.
406.5- 50 amp 240 volt receptacle shall be firmly mounted in place.
ELE16-00378 Final4/7/20164/8/20164/8/2016 9:20:46 AMAPASS
Garage Code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE16-01078 Electrical Rough-In4/7/20164/8/20164/8/2016 8:38:47 AMAPASS
8am inspection if at all possible please... Phone #: ###-#### Inspection requested via web by Stuart Welton
Flat conductor cable rough in ok cover