ELE02-00990
| Final | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | A | CANC |
|
|
marv ###-#### access to address from Ash Park lane see added p/s inspection 4/9/2002 2:34:33 PM
|
ELE02-00967
| Final | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by Inspector: 315 On 4/8/2002 4:33:57 PM meeting with B&B 8:30 ok 4/9/2002 10:32:17 AM
|
ELE02-00182
| Electrical Rough-In | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | A | PART |
|
|
###-#### call first to make sure homeowner is home. Conf,. only ok 4/9/2002 11:36:10 AM
|
ELE02-00673
| Final | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 04/08/2002 at 17:09:18. Contact: . ok 4/9/2002 10:56:39 AM
|
ELE01-03164
| Electrical Rough-In | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 04/08/2002 at 22:38:02. Contact: ###-####. basement ok 4/9/2002 12:10:21 PM
|
ELE02-00969
| Electrical Rough-In | 4/9/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 04/09/2002 at 08:21:38. Contact: ###-####. ok cor. made 4/9/2002 4:36:24 PM
|
ELE02-00152
| Electrical Rough-In | 4/9/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | NR |
|
|
DELBERT ###-#### dinning rm shall be kit. circuit add required outs where needed 312.5(A) 4/9/2002 6:49:52 PM
|
ELE02-00904
| Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted called 250.64(C) shall not splice GEC in lug 4/9/2002 5:54:02 PM
|
ELE02-00990
| Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | PART |
|
|
Added by Inspector: 315 On 4/9/2002 2:35:27 PM need to meet with contractor no p/s
|
ELE02-00990
| Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by Inspector: 315 On 4/9/2002 2:35:55 PM cor. posted called UAC 305.1 u/g and grd grid covered before inspection, and installed without permit and by non licesed persons(BMC 4-05-08) 110.12 seal unused openings around pvc, 300.12 shall maintain mechanicl cotinunity of raceway ent to lfnc, and flnc to pvc, with listed and approved fittings, 312.5(A) for grd wire entering bottom of cabinets 4/9/2002 5:22:35 PM
|
ELE02-00780
| Final | 4/8/2002 | 4/9/2002 | 4/9/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 04/08/2002 at 13:52:39. Contact: ###-####. cor. posted called 314.20 box in paneded wall shall be flush desk area, 314.29 shall not bury box jbox covered by the desk, 410.14 provide access to box , surface mounted flourescent fixture 4/9/2002 3:32:42 PM
|