Inspections for the day of: Wednesday, April 9, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01925 FIRE-Final Inspection4/7/20034/9/20034/9/2003 12:00:00 AMAFAIL
doug; Phone #: ###-#### I could not final the life safety due to the fire alarm permit still needing to be finaled. As far as life/safety signs need to be added at the fire dept. access gate and at the purge fan switch. Four roll down fire doors need to be tested. We tested one at the conveyor but it did not operate correctly. 4/9/2003 12:54:58 PM
FIR02-00359 INSP-Conference4/7/20034/9/20034/9/2003 12:00:00 AMADONE
###-#### Met with contractors about placement of the duct smoke detectors. Nothing could be completed since the mechanical engineer and the mechanical contractor were not present but the architect left with more knowledge of mechanical system 4/9/2003 9:52:03 AM
FIR03-00034 INSP-Final Inspection4/8/20034/9/20034/9/2003 12:00:00 AMAFAIL
I could not final project due to outstanding fire alarm plan issues. As for life safety the exit sign at the main exit needs repaired and door hardware for two group/offices near the main exit need approved hardware installed. They consist of double doors with manual flush bolts. Two existing fire extinguisher cabinets are mounted too high but contractor has letter from city giving approval to leave them at current hight. 4/9/2003 11:03:35 AM
FIR03-00034 INSP-Final Inspection4/9/20034/9/20034/9/2003 12:00:00 AMAPASS
Fire sprinklers finaled
FIR02-00478 INSP-Alarm Testing4/8/20034/9/20034/9/2003 12:00:00 AMPPART
duct smoke detectors tested out OK 4/9/2003 4:02:21 PM
FIR03-00052 INSP-Final Inspection4/7/20034/9/20034/9/2003 12:00:00 AMPFAIL
Outside electric alarm bell did not operate properly. All other items are ok 4/9/2003 3:33:35 PM