ELE08-00864
| Permanent Service | 4/9/2008 | 4/9/2008 | 4/9/2008 3:38:57 PM | P | PASS |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g rec. ok
|
ELE08-00864
| Final | 4/9/2008 | 4/9/2008 | 4/9/2008 3:38:27 PM | P | PASS |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
ELE08-00867
| Temporary Service | 4/9/2008 | 4/9/2008 | 4/9/2008 3:15:25 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
|
ELE08-00863
| Permanent Service | 4/9/2008 | 4/9/2008 | 4/9/2008 2:32:16 PM | P | FAIL |
|
|
stu ###-#### corr called install factory bond screw at meterbase, needs 2 grd rods, shall not use SMS for grds or bonds 250.8, conn for GEC
|
ELE08-00842
| Final | 4/8/2008 | 4/9/2008 | 4/9/2008 1:56:07 PM | P | PASS |
|
|
lance- attic fan- call 1/2 prior to insp Phone #: ###-#### ok
|
ELE08-00842
| Electrical Rough-In | 4/9/2008 | 4/9/2008 | 4/9/2008 1:55:29 PM | P | PASS |
|
|
lance- attic fan- call 1/2 prior to insp Phone #: ###-#### ok
|
ELE08-00819
| Rough-In Permanent Service | 4/9/2008 | 4/9/2008 | 4/9/2008 1:14:27 PM | P | PASS |
|
|
Rough In and Service Inspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe r/i p/s u/g new ok
|
ELE04-00123
| DOC - Permit Expired | 4/9/2008 | 4/9/2008 | 4/9/2008 10:25:07 AM | A | PASS |
|
|
no action on permit
|
ELE08-00070
| ELE-Aging Inspection | 4/9/2008 | 4/9/2008 | 4/9/2008 10:04:53 AM | | DONE |
|
|
|
ELE08-00070
| Final | 4/9/2008 | 4/9/2008 | 4/9/2008 10:04:44 AM | A | PASS |
|
|
ok
|
ELE08-00345
| Final | 4/8/2008 | 4/9/2008 | 4/9/2008 9:38:48 AM | A | FAIL |
|
|
michelle - please call for access Phone #: ###-#### corr called 210.12(B) needs afci for circuit, in new bedrm
|
ELE08-00846
| Final | 4/8/2008 | 4/9/2008 | 4/9/2008 9:37:50 AM | A | PASS |
|
|
michelle Phone #: ###-#### ok card signed
|
ELE08-00847
| Final | 4/8/2008 | 4/9/2008 | 4/9/2008 9:37:25 AM | A | PASS |
|
|
michelle Phone #: ###-#### okcard signed
|
ELE08-00068
| ELE-Aging Inspection | 4/9/2008 | 4/9/2008 | 4/9/2008 8:47:23 AM | | DONE |
|
|
|
ELE08-00068
| Final | 4/9/2008 | 4/9/2008 | 4/9/2008 8:47:16 AM | A | PASS |
|
|
ok
|
ELE08-00851
| Electrical Rough-In | 4/8/2008 | 4/9/2008 | 4/9/2008 8:15:24 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL walls and hard lids in restrms
|