BLD08-00491
| FIRE-Final Inspection | 4/8/2008 | 4/9/2008 | 4/10/2008 4:27:18 PM | P | PASS |
|
|
Fire life safety is acceptable pending approved door hardware at the main entry/exit- to be verified at structural final inspection.
|
BLD08-00496
| FIRE-Final Inspection | 4/8/2008 | 4/9/2008 | 4/10/2008 4:25:40 PM | P | PASS |
|
|
Fire life safety is satisfactory pending approved door hardware at the main entry/exit -to be verified at structural final.
|
FIR07-00837
| INSP-Final Inspection | 4/9/2008 | 4/9/2008 | 4/10/2008 4:22:15 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00692
| INSP-Final Inspection | 4/7/2008 | 4/9/2008 | 4/10/2008 4:21:19 PM | A | PASS |
|
|
Fire alarm passed inspection, permit finaled.
|
BLD08-00481
| FIRE-Final Inspection | 4/8/2008 | 4/9/2008 | 4/9/2008 4:54:32 PM | P | PASS |
|
|
Fire life safety inspection is satisfactory pending main entry door hardware is changed to approved type, NOTE: to be verified at the structural final per agreement.
|
BLD08-00495
| FIRE-Final Inspection | 4/8/2008 | 4/9/2008 | 4/9/2008 4:52:05 PM | P | FAIL |
|
|
Repair three exit signs and one EM light, one conference room is missing required fire alarm notification per the room use.
|
BLD08-00493
| FIRE-Final Inspection | 4/8/2008 | 4/9/2008 | 4/9/2008 4:50:23 PM | P | FAIL |
|
|
Blocked sprinkler coverage at a storage room, two EM lights need repaired, provide approved door hardware at the service elevator vestibule, hardware at the tenant main entry is not approved.
|
FIR07-00764
| INSP-Final Inspection | 4/9/2008 | 4/9/2008 | 4/9/2008 3:51:38 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR08-00180
| INSP-Sprinkler Rough-in/Hydro | 4/8/2008 | 4/9/2008 | 4/9/2008 3:50:18 PM | P | FAIL |
|
|
Inspection for cover at the womens and mens restrooms for the office area east side failed due to two pendent sprinkler heads which do not meet obstruction tables per NFPA 13.
|
FIR08-00116
| INSP-Final Inspection | 4/8/2008 | 4/9/2008 | 4/9/2008 3:48:20 PM | A | PASS |
|
|
Fire sprinkler rough-in and final inspections completed in conjunction, permit finaled.
|
FIR07-00764
| INSP-Alarm Testing | 4/7/2008 | 4/9/2008 | 4/9/2008 3:47:09 PM | A | PASS |
|
|
Fire alarm work passed inspection, tool placard indicating FA address to be installed as discussed, permit finaled.
|
FIR07-00963
| INSP-Final Inspection | 4/7/2008 | 4/9/2008 | 4/9/2008 3:45:42 PM | A | PASS |
|
|
Fire alarm field modifications passed testing, permit finaled.
|
FIR07-00751
| INSP-Final Inspection | 4/7/2008 | 4/9/2008 | 4/9/2008 3:43:29 PM | A | PASS |
|
|
Fire alarm permit finaled, inspection passed.
|
FIR07-00832
| INSP-Final Inspection | 4/7/2008 | 4/9/2008 | 4/9/2008 3:42:47 PM | A | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR07-00764
| INSP-Sprinkler Rough-in/Hydro | 4/7/2008 | 4/9/2008 | 4/7/2008 12:23:33 PM | A | CANC |
|
|
Tool specific Alarmed Supresion system.Refer to Micron project C9927- Install Bare wafer Stocker Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
|