FIR11-00668
| INSP-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 3:43:31 PM | P | PASS |
|
|
permit finaled
|
BLD11-02974
| FIRE-Final Inspection | 4/9/2012 | 4/9/2012 | 4/9/2012 3:14:30 PM | P | PASS |
|
|
life safety passed
|
FIR12-00148
| INSP-Final Inspection | 4/9/2012 | 4/9/2012 | 4/9/2012 3:13:33 PM | P | PASS |
|
|
permit finaled
|
FIR12-00161
| INSP-Sprinkler Rough-in | 4/6/2012 | 4/9/2012 | 4/9/2012 3:09:06 PM | P | PASS |
|
|
See the city approved plans for the locations of rooms where sprinkler piping cna be covered. Several issues that need corrected are marked on the plans.
|
BLD12-00652
| FIRE-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 2:32:22 PM | A | FAIL |
|
|
Provide annual inspection for the fire sprinkler system, Provide insepction for the fire extinguishers, repair exit signs/emergency lights, provide emergency lighting as discussed if it is missing, the doors with the mag locks need to meet IFC 1008.1.4.4
|
BLD11-03036
| FIRE-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 12:09:27 PM | P | PASS |
|
|
life safety passed
|
BLD11-03037
| FIRE-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 12:08:28 PM | P | PASS |
|
|
life safety passed
|
FIR12-00172
| INSP-Sprinkler Rough-in | 4/6/2012 | 4/9/2012 | 4/9/2012 12:07:28 PM | A | PASS |
|
|
sprinkler piping is ok to cover.
|
BLD11-02974
| FIRE-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 10:56:05 AM | A | FAIL |
|
|
Life safety will be ok to final when the project related fire alarm permit is addressed. Rescheduled for 3:00pm
|
FIR12-00148
| INSP-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 10:54:20 AM | A | FAIL |
|
|
Need one duct smoke detector oriented in the correct side of the duct and the correct length of sample tube provided. Also one other duct detector needs a sample tube provided that extends through the duct since it exceeds 3' in width. Re-scheduled for this afternoon at 3:00pm
|