Inspections for the day of: Monday, April 9, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00668 INSP-Final Inspection4/6/20124/9/20124/9/2012 3:43:31 PMPPASS
permit finaled
BLD11-02974 FIRE-Final Inspection4/9/20124/9/20124/9/2012 3:14:30 PMPPASS
life safety passed
FIR12-00148 INSP-Final Inspection4/9/20124/9/20124/9/2012 3:13:33 PMPPASS
permit finaled
FIR12-00161 INSP-Sprinkler Rough-in4/6/20124/9/20124/9/2012 3:09:06 PMPPASS
See the city approved plans for the locations of rooms where sprinkler piping cna be covered. Several issues that need corrected are marked on the plans.
BLD12-00652 FIRE-Final Inspection4/6/20124/9/20124/9/2012 2:32:22 PMAFAIL
Provide annual inspection for the fire sprinkler system, Provide insepction for the fire extinguishers, repair exit signs/emergency lights, provide emergency lighting as discussed if it is missing, the doors with the mag locks need to meet IFC 1008.1.4.4
BLD11-03036 FIRE-Final Inspection4/6/20124/9/20124/9/2012 12:09:27 PMPPASS
life safety passed
BLD11-03037 FIRE-Final Inspection4/6/20124/9/20124/9/2012 12:08:28 PMPPASS
life safety passed
FIR12-00172 INSP-Sprinkler Rough-in4/6/20124/9/20124/9/2012 12:07:28 PMAPASS
sprinkler piping is ok to cover.
BLD11-02974 FIRE-Final Inspection4/6/20124/9/20124/9/2012 10:56:05 AMAFAIL
Life safety will be ok to final when the project related fire alarm permit is addressed. Rescheduled for 3:00pm
FIR12-00148 INSP-Final Inspection4/6/20124/9/20124/9/2012 10:54:20 AMAFAIL
Need one duct smoke detector oriented in the correct side of the duct and the correct length of sample tube provided. Also one other duct detector needs a sample tube provided that extends through the duct since it exceeds 3' in width. Re-scheduled for this afternoon at 3:00pm