FIR12-00474
| FIR-Aging Inspection | 4/9/2013 | 4/9/2013 | 4/10/2013 7:28:43 AM | | NR |
|
|
Jeff is going to follow up on job status per phone conversation.
|
FIR13-00125
| INSP-Final Inspection | 4/9/2013 | 4/9/2013 | 4/9/2013 3:50:12 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00020
| INSP-Sprinkler Rough-in | 4/9/2013 | 4/9/2013 | 4/9/2013 3:36:37 PM | P | CANC |
|
|
Per lonny to be canceled Phone #: ###-####
|
FIR13-00074
| INSP-Sprinkler Rough-in | 4/9/2013 | 4/9/2013 | 4/9/2013 3:24:29 PM | P | PART |
|
|
The 2nd floor sprinkler piping can be covered. I noted one location where the pendant head is too close to a wall and another where a pendant head is overspaced in a office.
|
BLD12-02452
| FIRE-Final Inspection | 4/8/2013 | 4/9/2013 | 4/9/2013 2:45:25 PM | A | PASS |
|
|
Life safety passed. Sam in plan review was going to verify that the lever/thumbturn type locks on the ADA pocket doors is code compliant prior to the building inspection.
|
BLD13-00765
| FIRE-Final Inspection | 4/8/2013 | 4/9/2013 | 4/9/2013 2:43:42 PM | P | FAIL |
|
|
Provide for annual inspection for the fire extinguisher and provide single action hardware for the front door as discussed.
|
BLD12-00321
| FIRE-Final Inspection | 4/8/2013 | 4/9/2013 | 4/9/2013 12:46:24 PM | A | FAIL |
|
|
Provide fire dept. plan review comments, provide additional fire extinguisher at the car wash and on the mezzanine, provide exit discharge light at the main showroom exit (the one installed is too far away), remove exit sign at the east showroom exit per the approved plans, provide emergency lighting in the showroom entry vestible, repair non-functioning emergency lights and exit signs, provide final inspections for the fire sprinkler permits.
|
FIR12-00574
| INSP-Final Inspection | 4/8/2013 | 4/9/2013 | 4/9/2013 12:43:13 PM | A | FAIL |
|
|
The forward flush test failed and the plan modifications are not on site.
|
FIR12-00493
| INSP-Final Inspection | 4/8/2013 | 4/9/2013 | 4/9/2013 12:14:12 PM | A | PASS |
|
|
Permit finaled
|