Inspections for the day of: Thursday, April 9, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00683 ELE-Aging Inspection4/9/20154/9/20154/14/2015 3:01:12 PM DONE
Spoke with contractor will schedule
ELE15-00399 Final4/9/20154/9/20154/9/2015 3:02:59 PMPPASS
Inspection requested via web by Rowdy Monroe Outlet reported is a switched outlet. Final ok
ELE15-00642 Electrical Rough-In4/9/20154/9/20154/9/2015 2:29:10 PMPPASS
Lynn Phone #: ###-#### Grid rough in ok cover
ELE15-00836 Final4/9/20154/9/20154/9/2015 2:15:02 PMPPASS
call with questions Phone #: ###-#### Inspection requested via web by Don Lustig Final ok
ELE15-00970 Temporary Service4/9/20154/9/20154/9/2015 1:39:51 PMPCANC
John is out of town until later today. Call Tim if any issues. This inspection is only for trench inspection. Excavator is on site and is currently digging nearby sewer. Electrical conduit has been installed and photos have been taken Phone #: ###-#### Inspection requested via web by John Harvey Needed rough in inspection
ELE15-00970 Electrical Rough-In4/9/20154/9/20154/9/2015 1:25:17 PMPPASS
John is out of town until later today. Call Tim if any issues. This inspection is only for trench inspection. Excavator is on site and is currently digging nearby sewer. Electrical conduit has been installed and photos have been taken Phone #: ###-#### Inspection requested via web by John Harvey 2" service lateral and 1 1/4" feeder to garage rough in ok cover
ELE15-00516 Electrical Rough-In4/9/20154/9/20154/9/2015 1:06:00 PMPPART
Partial rough in, if you have any questions, please call Calvin. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Front soffit, North/South wall behind counter only rough in ok cover
ELE14-02213 Final4/9/20154/9/20154/9/2015 11:22:02 AMPPASS
Mike Phone #: ###-#### Final ok
ELE15-00720 Electrical Rough-In4/8/20154/9/20154/9/2015 11:10:04 AMPCANC
We will be there to walk thru it with you Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Inspection cancelled from web by: Dan Mitchell
ELE15-00963 Electrical Rough-In4/8/20154/9/20154/9/2015 10:50:34 AMAPASS
Floor heat in master bathroom. If no ones home the side door going into the house will be unlocked Phone #: ###-#### Inspection requested via web by TOM BICANDI Floor heat rough in ok cover
ELE15-00945 Final4/8/20154/9/20154/9/2015 10:19:54 AMAFAIL
Robert Phone #: ###-#### 210.63- a 120 volt 15 or 20 amp receptacle outlet shall be installed with in 25' of heat pump.
No answer at door, will not move fencing and other items to gain access to back yard . Wrong number provided for contact
ELE15-00936 Temporary Service4/8/20154/9/20154/9/2015 9:52:23 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
110.3- Grounded conductor not terminated.
406.5- 240 volt receptacle shall be securely fastened in place.
ELE15-00399 Final4/8/20154/9/20154/9/2015 9:32:26 AMAFAIL
Inspection requested via web by Rowdy Monroe 110.3 outlet in entry not working. No contact number provided. Left correction notice
ELE15-00964 Temporary Service4/8/20154/9/20154/9/2015 8:29:28 AMAPASS
Joe-please call with meet time Phone #: ###-#### t/s o/h n ok