FIR15-00015
| INSP-Final Inspection | 4/8/2015 | 4/9/2015 | 4/10/2015 3:31:46 PM | A | CANC |
|
|
To be rescheduled per Rick
|
FIR15-00038
| INSP-Sprinkler Rough-in | 4/8/2015 | 4/9/2015 | 4/9/2015 4:25:47 PM | P | PART |
|
|
Supply line rough-in passed. Just missing thrust blocks and one fitting on the remote FDC. Vault also needs to be installed prior to cover.
|
FIR15-00178
| INSP-Final Inspection | 4/9/2015 | 4/9/2015 | 4/9/2015 4:23:45 PM | P | CANC |
|
|
Overbooked. Will need to rescedule.
|
FIR15-00126
| INSP-Sprinkler Rough-in/Hydro | 4/9/2015 | 4/9/2015 | 4/9/2015 3:49:27 PM | A | PASS |
|
|
Overhead hydro test passed
|
FIR15-00182
| INSP-Sprinkler Rough-in | 4/8/2015 | 4/9/2015 | 4/9/2015 3:31:45 PM | A | PASS |
|
|
Underground is ok to cover from the street up to the end of the wrought iron fence
|
BLD15-01066
| FIRE-Final Inspection | 4/8/2015 | 4/9/2015 | 4/9/2015 2:44:42 PM | A | FAIL |
|
|
Provide address that is viewable from the street, provide annual inspection for the fire extinguisher, repair or remove emergency lights and remove the thumbturn deadbolt from the main exit.
|
FIR15-00214
| INSP-Alarm Testing | 4/8/2015 | 4/9/2015 | 4/9/2015 1:50:57 PM | A | FAIL |
|
|
Corrodor smoke detector did not release door mags.
|
BLD14-03470
| FIRE-Final Inspection | 4/8/2015 | 4/9/2015 | 4/9/2015 1:28:59 PM | A | PASS |
|
|
Life safety passed
|
FIR14-00691
| INSP-Final Inspection | 4/7/2015 | 4/9/2015 | 4/9/2015 11:15:40 AM | A | FAIL |
|
|
Today we tested the smoke and pull station at the FACP and the PIV and anti-freeze tampers in the Buffalo Club riser room. They functioned correctly. The smoke and pull activated the notification in the Buffalo Club. When the inspectors test was actiated in Harbor Freight neither flow switch at the Buffalo Club activated. Also no updated plans were available on site.
|
FIR14-00769
| INSP-Sprinkler Rough-in | 4/8/2015 | 4/9/2015 | 4/9/2015 9:53:04 AM | A | PASS |
|
|
Rough-in passed. One pendant is overspaced but will be checked at the tenting inspection.
|
BLD14-01856
| FIRE-Final Inspection | 4/9/2015 | 4/9/2015 | 4/9/2015 9:52:01 AM | P | PASS |
|
|
Life safety passed
|
BLD14-01740
| FIRE-Final Inspection | 4/9/2015 | 4/9/2015 | 4/9/2015 9:25:27 AM | P | PASS |
|
|
Life safety passed. Repair and demostrate exit discharge lights on front of building for building inspector
|
BLD14-01856
| FIRE-Final Inspection | 4/7/2015 | 4/9/2015 | 4/8/2015 3:48:53 PM | A | CANC |
|
|
Overbooked. Rescheduled for tomorrow morning
|
BLD14-01740
| FIRE-Final Inspection | 4/7/2015 | 4/9/2015 | 4/8/2015 3:47:49 PM | A | CANC |
|
|
Overbooked. Rescheduled for tomorrow morning.
|