Inspections for the day of: Thursday, April 9, 2015.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00015 INSP-Final Inspection4/8/20154/9/20154/10/2015 3:31:46 PMACANC
To be rescheduled per Rick
FIR15-00038 INSP-Sprinkler Rough-in4/8/20154/9/20154/9/2015 4:25:47 PMPPART
Supply line rough-in passed. Just missing thrust blocks and one fitting on the remote FDC. Vault also needs to be installed prior to cover.
FIR15-00178 INSP-Final Inspection4/9/20154/9/20154/9/2015 4:23:45 PMPCANC
Overbooked. Will need to rescedule.
FIR15-00126 INSP-Sprinkler Rough-in/Hydro4/9/20154/9/20154/9/2015 3:49:27 PMAPASS
Overhead hydro test passed
FIR15-00182 INSP-Sprinkler Rough-in4/8/20154/9/20154/9/2015 3:31:45 PMAPASS
Underground is ok to cover from the street up to the end of the wrought iron fence
BLD15-01066 FIRE-Final Inspection4/8/20154/9/20154/9/2015 2:44:42 PMAFAIL
Provide address that is viewable from the street, provide annual inspection for the fire extinguisher, repair or remove emergency lights and remove the thumbturn deadbolt from the main exit.
FIR15-00214 INSP-Alarm Testing4/8/20154/9/20154/9/2015 1:50:57 PMAFAIL
Corrodor smoke detector did not release door mags.
BLD14-03470 FIRE-Final Inspection4/8/20154/9/20154/9/2015 1:28:59 PMAPASS
Life safety passed
FIR14-00691 INSP-Final Inspection4/7/20154/9/20154/9/2015 11:15:40 AMAFAIL
Today we tested the smoke and pull station at the FACP and the PIV and anti-freeze tampers in the Buffalo Club riser room. They functioned correctly. The smoke and pull activated the notification in the Buffalo Club. When the inspectors test was actiated in Harbor Freight neither flow switch at the Buffalo Club activated. Also no updated plans were available on site.
FIR14-00769 INSP-Sprinkler Rough-in4/8/20154/9/20154/9/2015 9:53:04 AMAPASS
Rough-in passed. One pendant is overspaced but will be checked at the tenting inspection.
BLD14-01856 FIRE-Final Inspection4/9/20154/9/20154/9/2015 9:52:01 AMPPASS
Life safety passed
BLD14-01740 FIRE-Final Inspection4/9/20154/9/20154/9/2015 9:25:27 AMPPASS
Life safety passed. Repair and demostrate exit discharge lights on front of building for building inspector
BLD14-01856 FIRE-Final Inspection4/7/20154/9/20154/8/2015 3:48:53 PMACANC
Overbooked. Rescheduled for tomorrow morning
BLD14-01740 FIRE-Final Inspection4/7/20154/9/20154/8/2015 3:47:49 PMACANC
Overbooked. Rescheduled for tomorrow morning.