Inspections for the day of: Thursday, April 9, 2015.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTim Frost
TitleFIRE PLANS EXAMINER
Phone #208-608-7110
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00866 INSP-Sprinkler Rough-in4/8/20154/9/20154/9/2015 12:00:00 AMAPASS
Passed

However, I had a conference with the super. I told him there could be a potential problem with freeze ups where the insulation butts together directly above the sprinkler piping.
FIR14-00815 INSP-Sprinkler Rough-in4/7/20154/9/20154/9/2015 12:00:00 AMPPASS
Area 1, level 4, Wet System. OK for cover except the floor will require an insulation inspection. Access will need to be provided for observation.

One room with sprinkler coverage that needs to be slightly altered. On one room with open pipe no sprinkller. Will verify corrections with Jeff on 04-10-2015.