Inspections for the day of: Monday, April 9, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00442 INSP-Sprinkler Rough-in4/9/20184/9/20184/9/2018 4:44:54 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
FIR18-00051 INSP-Sprinkler Rough-in4/6/20184/9/20184/9/2018 4:03:51 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above various hardlids, notated city approved drawings with red ink areas approved for cover.
BLD18-00225 FIRE-Final Inspection4/6/20184/9/20184/9/2018 2:43:16 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work complete.
FIR18-00245 INSP-Final Inspection4/9/20184/9/20184/9/2018 1:51:03 PMPPASS
Final fire alarm inspection for scope of work complete.
BLD17-03590 FIRE-Final Inspection4/9/20184/9/20184/9/2018 1:46:24 PMPFAIL
Provide exit discharge illumination that is connected to an emergency power supply. Provide maximum occupancy placard for training classroom. Mount fire extinguishers in discussed locations. Repair emergency light in southwest corner cubicle area (Light that needs repaired is on the east side of mentioned area).
FIR18-00233 INSP-Final Inspection4/9/20184/9/20184/9/2018 1:42:21 PMPPASS
Final fire alarm inspection for scope of work complete.
FIR18-00193 INSP-Final Inspection4/9/20184/9/20184/9/2018 1:41:52 PMPPASS
Final fire alarm inspection for scope of work complete.
FIR18-00111 INSP-Final Inspection4/6/20184/9/20184/9/2018 1:41:12 PMPPASS
Final fire sprinkler inspection for fire sprinkler inspection complete. Final inspection for pre-action system complete.
FIR18-00111 INSP-Sprinkler Rough-in4/9/20184/9/20184/9/2018 1:40:15 PMPPASS
Rough to cover inspection for area of work complete, approved for cover.
BLD18-00718 FIRE-Final Inspection4/9/20184/9/20184/9/2018 11:03:36 AMPFAIL
Fire extinguishers need annual inspection performed (basement and main level extinguishers), tags on extinguishers indicate 2015 for last inspection. Exit lights/emergency lighting needs to be serviced and operable under emergency power. Provide inspection report for last annual fire alarm inspection. Provide emergency lighting for egress discharge as per note number 6 of building permit fire code review comments.