Inspections for the day of: Tuesday, April 9, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00023 Final4/9/20194/9/20194/9/2019 3:23:55 PMPPASS
Lori Phone #: ###-####
Final ok
ELE19-00023 Electrical Rough-In4/9/20194/9/20194/9/2019 3:06:44 PMPPASS
Lori Phone #: ###-####
Listing and disconnecting means confirmed. Rough in ok
ELE18-04138 Electrical Rough-In4/9/20194/9/20194/9/2019 2:55:51 PMPPASS
Ceilings for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel Ceilings rough in ok cover
ELE18-01608 Conference4/9/20194/9/20194/9/2019 2:55:34 PMPDONE
Discussed ceilings in bathrooms of EO Wilson building. Access shall be provided to fit a full body above ceiling to access emergency ballast of luminaires in bathroom and bathroom entrance. Ceiling support system shall not be used to support luminaires, cables, or conduits unless manufacturers instructions state other wise
ELE19-01001 Final4/9/20194/9/20194/9/2019 2:29:47 PMPPASS
Jose- please call if any questions Phone #: ###-#### Final ok
ELE19-01201 Permanent Service4/8/20194/9/20194/9/2019 2:29:16 PMAPASS
Please let me know when done Phone #: ###-#### Inspection requested via web by Thomas wilson
p/s u/g n ok
ELE19-01075 Electrical Rough-In4/9/20194/9/20194/9/2019 2:02:57 PMPPASS
Lock box code 8463 located on the hand rail in stairwell. Looking for OK to cover floor box in conference room, and wall in break room. Phone #: ###-#### Inspection requested via web by Dean Gernaat
Area noted rough in ok cover
ELE19-01043 Rough-In Permanent Service4/9/20194/9/20194/9/2019 1:49:40 PMPPASS
Please call 30min in advance so I can meet you there. Phone #: ###-#### Inspection requested via web by Jason Wicks
Wrong number listed correct number ###-####.
Electrical contractor has replaced all wiring associated with kitchen, small appliance circuits and seperated 15 and 20 amp circuits so correct wire size is present where needed.
As per Daryl DeGrange if electrical contractor takes responsibility for wiring in kitchen and bathroom areas additional drywall does not need to be removed.
Electrical contractor confirmed he would be responsible for all wiring in kitchen and bathroom areas.
250.64- Grounding electrode conductors shall be continuous to main disconnecting means.
250.140- Range and dryer receptacles shall be 4 wire, appliance frames shall not be bonded through grounded conductor.
Rough in of patch holes ok cover. p/s o/h rec ok
ELE19-01202 Rough-In Permanent Service4/9/20194/9/20194/9/2019 12:45:37 PMPPASS
Call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser
OKed with general contractor promise not to foam seal prior to inspection again. Nice job!
Rough in ok cover p/s u/g n ok
ELE19-01246 Permanent Service4/8/20194/9/20194/9/2019 11:21:44 AMAPASS
Please let me know when done Phone #: ###-#### Inspection requested via web by Thomas wilson p/s u/g n ok
ELE19-00350 Final4/8/20194/9/20194/9/2019 10:32:01 AMAPASS
Will Phone #: ###-#### Final ok
ELE19-00350 Electrical Rough-In4/9/20194/9/20194/9/2019 10:31:40 AMPPASS
Will Phone #: ###-####
Grid rough in ok cover
ELE19-01166 Temporary Service4/8/20194/9/20194/9/2019 10:01:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE19-01202 Rough-In Permanent Service4/8/20194/9/20194/9/2019 9:58:21 AMAFAIL
call with any questions, thank you Phone #: ###-#### Inspection requested via web by kim grundhauser
BCC 4 05 23- It shall be unlawful for any person, to cover in any way or conceal any electrical wiring ,cable, conduit or other equipment until the same has been inspected and approved by an electrical inspector.
Remove all caulking around boxes and foam applied to bored holes where wiring is run and recall
ELE19-00602 Electrical Rough-In4/8/20194/9/20194/9/2019 9:21:25 AMAPASS
Cover for NE concrete walls. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
N.E. corner wall pour rough in ok cover