Inspections for the day of: Tuesday, April 9, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01382 Rough-in4/9/20194/9/20194/9/2019 4:08:40 PMPFAIL
Phone #: ###-#### Inspection requested via web by Joseph Profitt
- EF6 is the wrong flex size per the prints
- exhaust trunk and supply duct into storage room needs sealed still
- outside air duct located in the soffit needs to be insulated
MEC19-00389 Final4/9/20194/9/20194/9/2019 2:57:03 PMPPASS
corrections made, re-inspect please. garage code 7573.
thanks Phone #: ###-#### Inspection requested via web by Oleg Chervak
- final ok
MEC17-05830 Final4/8/20194/9/20194/9/2019 2:21:10 PMPPASS
please call home owner 30 min. in advance.
###-#### Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- final ok
MEC19-01352 Final4/8/20194/9/20194/9/2019 2:08:49 PMPFAIL
Please call home owner on the way, ###-#### and call Brett with any questions about the install ###-#### Phone #: ###-#### Inspection requested via web by Brett Shannon
- sediment trap needs to be installed after shut off valve
- A/C breaker size needs to be a 20 amp
MEC19-00427 Final4/9/20194/9/20194/9/2019 1:55:10 PMPPASS
If front door is locked, key is on electric panel on right side of house. Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- final ok
MEC19-01349 Rough-in4/9/20194/9/20194/9/2019 1:34:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Joseph Profitt
- R/I ok
- need to check equipment and man j at final
MEC19-01403 Pressure Test4/8/20194/9/20194/9/2019 1:06:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by Frank Marturello
- 20lb gas pressure test fail gauge was under 20lb
- 5lb flue test was under 5lb
MEC19-01403 Rough-in4/8/20194/9/20194/9/2019 1:05:32 PMPFAIL
Phone #: ###-#### Inspection requested via web by Frank Marturello
- pressure tests failed
MEC19-01427 Final4/9/20194/9/20194/9/2019 12:13:20 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek
MEC18-02612 Final4/4/20194/9/20194/9/2019 10:58:26 AMAPASS
Please call homeowner 30 minutes in advance for access at ###-#### and call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs
- final ok
MEC19-01365 Rough-in4/8/20194/9/20194/9/2019 9:35:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace R/I ok
MEC18-03675 Mec-Aging Inspection4/9/20194/9/20194/9/2019 9:18:35 AM DONE
WIP
MEC19-01397 Rough-in4/8/20194/9/20194/9/2019 9:15:48 AMAPASS
Andy ###-####
manual in bottom of unit Phone #: ###-#### Inspection requested via web by Mike Almanza
- fireplace R/I ok
MEC18-03663 Mec-Aging Inspection4/9/20194/9/20194/9/2019 9:08:31 AM DONE
Called Fireplace Wholesale and talked with office about their mechanical aging permit. Schedule inspection with homeowner if work is finished. Permit will expire in 180 days if not active
MEC18-05250 Final4/5/20194/9/20194/5/2019 10:06:19 AMACANC
Call Jason @ ###-#### with any issues. Phone #: ###-#### >> Inspection requested via web by Angie Maguire Inspection cancelled from web by: Angie Maguire