FIR20-00062
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 2:21:54 PM | P | DONE |
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Overhead rough/hydro/tenting. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00063
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 2:21:41 PM | P | DONE |
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00064
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 2:21:27 PM | P | DONE |
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00065
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 2:21:14 PM | P | DONE |
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00066
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 2:20:49 PM | P | DONE |
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD20-00131
| FIRE-Final Inspection | 4/8/2020 | 4/9/2020 | 4/9/2020 2:18:29 PM | A | PASS |
|
|
Building does not have fire sprinkler as shown in project description, no sprinklers, no fire alarms, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for scope of work is complete, signature card not presented at time of inspection, no signature given.
Tom **Cleared** Phone #: ###-####
|
FIR19-00516
| INSP-Sprinkler Rough-in | 4/9/2020 | 4/9/2020 | 4/9/2020 11:31:09 AM | P | CANC |
|
|
Rescheduled to coincide with ESI inspection times, inspection request moved to 10APR2020 AM time block, this request is cancelled.
Jon Beazer is the contact as well as Tony Cetani ###-####. The inspection will be for the fifth floor. Thanks (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00061
| INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 10:29:13 AM | P | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00062
| INSP-Sprinkler Rough-in | 4/9/2020 | 4/9/2020 | 4/9/2020 9:46:26 AM | A | FAIL |
|
|
Rough in inspection is complete, tenting has been removed by other trades in numerous areas, cover is not approved until tenting is corrected.
|