ELE02-01270
| Rough-In Permanent Service | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | PART |
|
|
###-#### darrel r/i ok 5/1/2002 1:52:47 PM
|
ELE02-01090
| Rough-In Permanent Service | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 04/30/2002 at 09:29:54. Contact: ###-####. needs to strap MC within 12 inches of soffit lights 5/1/2002 1:52:32 PM
|
ELE02-01281
| Rough-In Permanent Service | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | FAIL |
|
|
r/i & ser john ###-#### cor.posted called 314.43 M bath outlets screws not allowed in box 314.20 outside boxes not flush with siding, 210.52(A)(B) outlet spacing M bedrm, needs outlet right of sider door in dinning rm shall be served by kit. circuit, living rm outlet shall not serve dinning 5/1/2002 10:42:15 AM
|
ELE01-04216
| Electrical Rough-In | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 05/01/2002 at 10:54:00. Contact: ###-####. cover for soffit ok correction posted for contractor 400.8(5) on his request 5/1/2002 3:43:34 PM
|
ELE02-01272
| Electrical Rough-In | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PART |
|
|
###-#### HAROLD added walls, and ceiling ok 5/1/2002 4:40:25 PM
|
ELE02-01057
| Final | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | FAIL |
|
|
###-#### HAROLD gfci not wired properly, and no power to some outlets, ok to cover ceiling 5/1/2002 4:41:27 PM
|
ELE02-01217
| Electrical Rough-In | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PASS |
|
|
###-#### doug u/g for parking lot ok 5/1/2002 5:20:55 PM
|