Inspections for the day of: Wednesday, May 1, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00101 FIRE-Final Inspection4/30/20025/1/20025/1/2002 12:00:00 AMAFAIL
duct detector that was installed was mounted outside. It is not listed for exterior use 5/1/2002 9:48:18 AM
BLD02-00474 FIRE-Final Inspection4/30/20025/1/20025/1/2002 12:00:00 AMAFAIL
Provide suite number, provide fire extinguisher and provide ADA approved hardware on restroom door 5/1/2002 9:12:11 AM
BLD01-02240 FIRE-Hydro test above ground4/30/20025/1/20025/1/2002 12:00:00 AMAFAIL
unable to perform hydro test due to faulty valve, unerground flush ok 5/1/2002 2:47:22 PM
FIR02-00160 INSP-Final Inspection4/30/20025/1/20025/1/2002 12:00:00 AMPPART
sprinkler rough-in ok. waiting for alarm connection for final 5/1/2002 4:09:25 PM
BLD01-00662 FIRE-Final Inspection5/1/20025/1/20025/1/2002 12:00:00 AMPFAIL
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer 5/1/2002 1:38:11 PM
FIR02-00145 INSP-Sprinkler Rough-in/Hydro5/1/20025/1/20025/1/2002 12:00:00 AMPPART
Hydro test OK 5/1/2002 4:29:45 PM
FIR01-00514 INSP-Final Inspection5/1/20025/1/20025/1/2002 12:00:00 AMPFAIL
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer
FIR02-00060 INSP-Supply line flush5/1/20025/1/20025/1/2002 12:00:00 AMPPASS
underground flush OK