BLD02-00101
| FIRE-Final Inspection | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | FAIL |
|
|
duct detector that was installed was mounted outside. It is not listed for exterior use 5/1/2002 9:48:18 AM
|
BLD02-00474
| FIRE-Final Inspection | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | FAIL |
|
|
Provide suite number, provide fire extinguisher and provide ADA approved hardware on restroom door 5/1/2002 9:12:11 AM
|
BLD01-02240
| FIRE-Hydro test above ground | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | A | FAIL |
|
|
unable to perform hydro test due to faulty valve, unerground flush ok 5/1/2002 2:47:22 PM
|
FIR02-00160
| INSP-Final Inspection | 4/30/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PART |
|
|
sprinkler rough-in ok. waiting for alarm connection for final 5/1/2002 4:09:25 PM
|
BLD01-00662
| FIRE-Final Inspection | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | FAIL |
|
|
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer 5/1/2002 1:38:11 PM
|
FIR02-00145
| INSP-Sprinkler Rough-in/Hydro | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PART |
|
|
Hydro test OK 5/1/2002 4:29:45 PM
|
FIR01-00514
| INSP-Final Inspection | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | FAIL |
|
|
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer
|
FIR02-00060
| INSP-Supply line flush | 5/1/2002 | 5/1/2002 | 5/1/2002 12:00:00 AM | P | PASS |
|
|
underground flush OK
|