BLD03-01845
| FIRE-Final Inspection | 4/24/2006 | 4/24/2006 | | A | |
|
|
For final status
|
BLD05-00087
| FIRE-Conference | 4/28/2006 | 5/1/2006 | 5/2/2006 8:21:55 AM | A | DEFR |
|
|
To be completed 5/2 as discussed.
|
FIR05-00707
| INSP-Sprinkler Rough-in/Hydro | 5/1/2006 | 5/1/2006 | 5/2/2006 8:19:10 AM | P | PART |
|
|
Overhead rough-in is acceptable for cover at the 1st and 2nd floors only, need inspection for cold cavity protection at the 3rd floor prior to cover at this area.
|
FIR05-00710
| INSP-Sprinkler Rough-in/Hydro | 5/1/2006 | 5/1/2006 | 5/2/2006 8:16:37 AM | P | PART |
|
|
Third floor is approved for cover, insulation at one area repaired while on site, missing nailer plate has been installed.
|
FIR06-00112
| INSP-Final Inspection | 4/28/2006 | 5/1/2006 | 5/1/2006 1:59:31 PM | A | PASS |
|
|
Fire alarm corrections have been verified, permit work passed final inspection.
|
BLD05-03442
| FIRE-Final Inspection | 4/25/2006 | 5/1/2006 | 5/1/2006 11:43:26 AM | A | PASS |
|
|
|
FIR05-00886
| INSP-Final Inspection | 4/24/2006 | 5/1/2006 | 5/1/2006 11:42:45 AM | A | PASS |
|
|
Fire alarm work is satisfactory.
|
FIR06-00052
| INSP-Final Inspection | 4/24/2006 | 5/1/2006 | 5/1/2006 11:41:43 AM | A | PASS |
|
|
Vesda system functioned properly, fire alarm passed field inspection.
|
BLD05-02737
| FIRE-Final Inspection | 4/25/2006 | 5/1/2006 | 5/1/2006 11:40:07 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR05-00649
| INSP-Final Inspection | 4/24/2006 | 5/1/2006 | 5/1/2006 11:39:12 AM | A | PASS |
|
|
Correction items have been completed, fire alarm passed inspection.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 4/28/2006 | 5/1/2006 | 5/1/2006 11:37:07 AM | A | PART |
|
|
Overhead fire sprinkler rough-in for the 7th floor is good for cover, need to relocate two overspaced uprights at the SE stair landing, one pendent in SW guest room is overspaced, need to provide approved plans showing design changes and added heads at guest room soffits.
|
BLD06-00351
| FIRE-Final Inspection | 4/25/2006 | 5/1/2006 | 5/1/2006 12:00:00 AM | A | CANC |
|
|
craig pager #99710; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles per craig 4/25/2006
|
FIR06-00110
| INSP-Final Inspection | 4/24/2006 | 5/1/2006 | 4/25/2006 12:00:00 AM | A | CANC |
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles per craig
|