Inspections for the day of: Tuesday, May 1, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00798 FIR-Aging Inspection5/1/20075/1/20075/7/2007 1:43:54 PM DONE
Pending inspection request.
FIR06-00800 INSP-Sprinkler Rough-in/Hydro4/30/20075/1/20075/2/2007 10:43:54 AMPFAIL
Shell OH wet system hydrostatic test failed due to pressure loss at the guages and visible leakage at the 6th and 3rd floors.
FIR07-00255 INSP-Sprinkler Rough-in5/1/20075/1/20075/2/2007 7:17:50 AMPPASS
Fire sprinkler system modifications passed inspection.
FIR06-00639 INSP-Final Inspection5/1/20075/1/20075/1/2007 2:52:55 PMPPASS
Fire sprinkler permit finaled.
BLD05-02750 FIRE-Final Inspection5/1/20075/1/20075/1/2007 2:51:59 PMPNR
daryl - fire life safety - as early as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
BLD05-00926 FIRE-Final Inspection5/1/20075/1/20075/1/2007 2:50:45 PMPNR
Need project related fire sprinkler final prior to life safety inspection request.
BLD05-02204 FIRE-Final Inspection5/1/20075/1/20075/1/2007 2:49:10 PMPFAIL
Still missing approved door hardware at the main entry/exit first floor, building address numbers are installed too low, the project related fire alarm permit is not ready for final, plastic covers are still in place at the unit single station SD's on all floors.
FIR06-00495 INSP-Final Inspection5/1/20075/1/20075/1/2007 2:44:46 PMPFAIL
Tamper switch at the first floor control valve still does not function, weatherproof covers at the 5th floor outdoor notification devices are not yet installed, provide map at the panel as discussed.
FIR06-00939 INSP-Supply line flush5/1/20075/1/20075/1/2007 1:58:28 PMPPART
UG fire supply line flush completed satisfactory per inspection by S. Arellano.
FIR07-00011 INSP-Sprinkler Rough-in/Hydro5/1/20075/1/20075/1/2007 1:56:53 PMPPART
Overhead FS as noted on approved plan set is good for cover at the drop ceilings.
BLD07-00711 FIRE-Final Inspection4/30/20075/1/20075/1/2007 12:26:02 PMAPASS
Insulation install is acceptable, noted one small area to be retaped, also need to remove the construction dust covers at four smoke detectors during the interm period until new construction begins.
FIR07-00292 INSP-Sprinkler Rough-in/Hydro4/30/20075/1/20075/1/2007 12:22:49 PMAPART
OH rough-in is acceptable for cover at the remainder of drop ceiling areas within the tenant remodel, noted one leaking joint at the back hallway adjacent to the restroom vestibule.
BLD06-03412 FIRE-Sprinkler Rough-in4/30/20075/1/20075/1/2007 12:19:45 PMADEFR
Inspection was intended for the project related fire sprinkler permit work.
FIR06-00897 INSP-Final Inspection4/30/20075/1/20074/30/2007 2:55:33 PMAPASS
UG fire supply line permit finaled.