FIR06-00798
| FIR-Aging Inspection | 5/1/2007 | 5/1/2007 | 5/7/2007 1:43:54 PM | | DONE |
|
|
Pending inspection request.
|
FIR06-00800
| INSP-Sprinkler Rough-in/Hydro | 4/30/2007 | 5/1/2007 | 5/2/2007 10:43:54 AM | P | FAIL |
|
|
Shell OH wet system hydrostatic test failed due to pressure loss at the guages and visible leakage at the 6th and 3rd floors.
|
FIR07-00255
| INSP-Sprinkler Rough-in | 5/1/2007 | 5/1/2007 | 5/2/2007 7:17:50 AM | P | PASS |
|
|
Fire sprinkler system modifications passed inspection.
|
FIR06-00639
| INSP-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 2:52:55 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-02750
| FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 2:51:59 PM | P | NR |
|
|
daryl - fire life safety - as early as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD05-00926
| FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 2:50:45 PM | P | NR |
|
|
Need project related fire sprinkler final prior to life safety inspection request.
|
BLD05-02204
| FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 2:49:10 PM | P | FAIL |
|
|
Still missing approved door hardware at the main entry/exit first floor, building address numbers are installed too low, the project related fire alarm permit is not ready for final, plastic covers are still in place at the unit single station SD's on all floors.
|
FIR06-00495
| INSP-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 2:44:46 PM | P | FAIL |
|
|
Tamper switch at the first floor control valve still does not function, weatherproof covers at the 5th floor outdoor notification devices are not yet installed, provide map at the panel as discussed.
|
FIR06-00939
| INSP-Supply line flush | 5/1/2007 | 5/1/2007 | 5/1/2007 1:58:28 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory per inspection by S. Arellano.
|
FIR07-00011
| INSP-Sprinkler Rough-in/Hydro | 5/1/2007 | 5/1/2007 | 5/1/2007 1:56:53 PM | P | PART |
|
|
Overhead FS as noted on approved plan set is good for cover at the drop ceilings.
|
BLD07-00711
| FIRE-Final Inspection | 4/30/2007 | 5/1/2007 | 5/1/2007 12:26:02 PM | A | PASS |
|
|
Insulation install is acceptable, noted one small area to be retaped, also need to remove the construction dust covers at four smoke detectors during the interm period until new construction begins.
|
FIR07-00292
| INSP-Sprinkler Rough-in/Hydro | 4/30/2007 | 5/1/2007 | 5/1/2007 12:22:49 PM | A | PART |
|
|
OH rough-in is acceptable for cover at the remainder of drop ceiling areas within the tenant remodel, noted one leaking joint at the back hallway adjacent to the restroom vestibule.
|
BLD06-03412
| FIRE-Sprinkler Rough-in | 4/30/2007 | 5/1/2007 | 5/1/2007 12:19:45 PM | A | DEFR |
|
|
Inspection was intended for the project related fire sprinkler permit work.
|
FIR06-00897
| INSP-Final Inspection | 4/30/2007 | 5/1/2007 | 4/30/2007 2:55:33 PM | A | PASS |
|
|
UG fire supply line permit finaled.
|