Inspections for the day of: Thursday, May 1, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00026 Electrical Rough-In5/1/20085/1/20085/1/2008 3:50:19 PMPPART
ken Phone #: ###-####
upper levels ok
ELE08-01096 Electrical Rough-In5/1/20085/1/20085/1/2008 2:41:43 PMPPASS
This is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten
ELE08-01096 Final5/1/20085/1/20085/1/2008 2:41:32 PMPPASS
This is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten
ELE08-00958 Permanent Service4/30/20085/1/20085/1/2008 1:24:52 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk
P/S U/G N Ok
ELE08-01093 Electrical Rough-In4/30/20085/1/20085/1/2008 12:31:57 PMAPART
bob Phone #: ###-####
Garage R/I Ok
underground to garage has not been seen and electrode is not connected yet.
ELE08-01090 Electrical Rough-In4/30/20085/1/20085/1/2008 11:48:50 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters
ELE08-00510 Electrical Rough-In4/30/20085/1/20085/1/2008 10:31:35 AMAPART
Inspect trench for parking lot light Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
U/G OK
ELE08-00496 Final4/30/20085/1/20085/1/2008 10:18:59 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lloyd Looney
ELE08-00249 Final5/1/20085/1/20085/1/2008 10:17:25 AMAPASS
Scheduled by a contractor via Hello! on 5/1/2008 at 7:30:30 AM. Contact: ###-####.final ok with survey for
GFCI protect fan/light per listing instructions.
ELE08-00658 Final4/30/20085/1/20085/1/2008 9:25:41 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
uncover work done prior to permit being taken out insure correct room count add service to permit.
2" imc or ridged required for mast support, bond raceway between meter and panel, GEC not permited in metal raceway without bonding both ends, and cable to enter through proper fittings
ELE08-00597 Electrical Rough-In4/30/20085/1/20085/1/2008 8:28:59 AMAPASS
john - floor heat - first thing in the morning if possible Phone #: ###-####