Inspections for the day of: Thursday, May 1, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00045 INSP-Sprinkler Rough-in5/1/20085/1/20085/5/2008 9:27:13 AMPPART
OH fire sprinkler okayed for cover at the hard lid intermediate landing adjacent to the east stairway.
FIR08-00228 INSP-Final Inspection5/1/20085/1/20085/1/2008 4:51:36 PMPPASS
Noted corrections are complete, fire sprinkler permit scope finaled.
BLD08-00220 FIRE-Final Inspection5/1/20085/1/20085/1/2008 4:50:44 PMPPASS
Life safety final okay per D. Hannah
FIR08-00106 INSP-Final Inspection4/28/20085/1/20085/1/2008 4:49:56 PMAPASS
Fire sprinkler permit finaled.
BLD08-00155 FIRE-Final Inspection5/1/20085/1/20085/1/2008 1:54:54 PMPPART
Fire life safety okayed for the west half of the phase two remodel as noted on plans with today's date, hardware at one small conference room to be replaced as agreed.
BLD08-00879 FIRE-Final Inspection5/1/20085/1/20085/1/2008 1:15:19 PMPFAIL
Provide approved door hardware and signage at the main entry/exit, post missing building address, provide and post one tagged fire extinguisher as discussed, hardware at the back door from the work area is not approved.
BLD08-00706 FIRE-Final Inspection4/30/20085/1/20085/1/2008 12:33:54 PMAFAIL
Need to provide signage at the main entry/exit door " door to remain unlocked while building is occupied", post the fire extinguisher as discussed, door hardware at the restroom is not approved, if two exits are required the back doors do not meet egress requirements.
BLD08-00514 FIRE-Final Inspection4/30/20085/1/20085/1/2008 11:47:51 AMAPASS
Fire life safety inspection completed satisfactory in conjunction with project related fire alarm work.
FIR08-00252 INSP-Final Inspection4/30/20085/1/20085/1/2008 11:45:46 AMAPASS
After hours fire alarm inspection completed satisfactory per the scope of permit work, one non-functional strobe appliance replaced while on site, cd at two locations adjusted, programming for three existing and now non-required smoke detectors for door holder release to be corrected or remove the devices prior to next scheduled alarm inspection for verification, nac batteries tested okay.
BLD07-03242 FIRE-Final Inspection4/30/20085/1/20085/1/2008 11:37:08 AMAPASS
Noted corrections have been completed with the exception of several interior doors yet to be installed-this item can be verified at structural inspection per discussion, temporary suite address is posted until permanent signage is delivered.
FIR08-00183 INSP-Final Inspection4/30/20085/1/20085/1/2008 11:33:56 AMAPASS
Fire alarm work passed functional testing, pemit finaled.
FIR08-00314 INSP-Final Inspection4/30/20085/1/20085/1/2008 11:32:57 AMAPASS
Hood suppression system operated correctly under test conditions, permit finaled.