FIR08-00045
| INSP-Sprinkler Rough-in | 5/1/2008 | 5/1/2008 | 5/5/2008 9:27:13 AM | P | PART |
|
|
OH fire sprinkler okayed for cover at the hard lid intermediate landing adjacent to the east stairway.
|
FIR08-00228
| INSP-Final Inspection | 5/1/2008 | 5/1/2008 | 5/1/2008 4:51:36 PM | P | PASS |
|
|
Noted corrections are complete, fire sprinkler permit scope finaled.
|
BLD08-00220
| FIRE-Final Inspection | 5/1/2008 | 5/1/2008 | 5/1/2008 4:50:44 PM | P | PASS |
|
|
Life safety final okay per D. Hannah
|
FIR08-00106
| INSP-Final Inspection | 4/28/2008 | 5/1/2008 | 5/1/2008 4:49:56 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD08-00155
| FIRE-Final Inspection | 5/1/2008 | 5/1/2008 | 5/1/2008 1:54:54 PM | P | PART |
|
|
Fire life safety okayed for the west half of the phase two remodel as noted on plans with today's date, hardware at one small conference room to be replaced as agreed.
|
BLD08-00879
| FIRE-Final Inspection | 5/1/2008 | 5/1/2008 | 5/1/2008 1:15:19 PM | P | FAIL |
|
|
Provide approved door hardware and signage at the main entry/exit, post missing building address, provide and post one tagged fire extinguisher as discussed, hardware at the back door from the work area is not approved.
|
BLD08-00706
| FIRE-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 12:33:54 PM | A | FAIL |
|
|
Need to provide signage at the main entry/exit door " door to remain unlocked while building is occupied", post the fire extinguisher as discussed, door hardware at the restroom is not approved, if two exits are required the back doors do not meet egress requirements.
|
BLD08-00514
| FIRE-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 11:47:51 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory in conjunction with project related fire alarm work.
|
FIR08-00252
| INSP-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 11:45:46 AM | A | PASS |
|
|
After hours fire alarm inspection completed satisfactory per the scope of permit work, one non-functional strobe appliance replaced while on site, cd at two locations adjusted, programming for three existing and now non-required smoke detectors for door holder release to be corrected or remove the devices prior to next scheduled alarm inspection for verification, nac batteries tested okay.
|
BLD07-03242
| FIRE-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 11:37:08 AM | A | PASS |
|
|
Noted corrections have been completed with the exception of several interior doors yet to be installed-this item can be verified at structural inspection per discussion, temporary suite address is posted until permanent signage is delivered.
|
FIR08-00183
| INSP-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 11:33:56 AM | A | PASS |
|
|
Fire alarm work passed functional testing, pemit finaled.
|
FIR08-00314
| INSP-Final Inspection | 4/30/2008 | 5/1/2008 | 5/1/2008 11:32:57 AM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions, permit finaled.
|