Inspections for the day of: Thursday, May 1, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00054 INSP-Final Inspection5/1/20085/1/20085/1/2008 4:34:39 PMAPASS
Permit finaled
FIR07-00213 INSP-Sprinkler Rough-in4/30/20085/1/20085/1/2008 3:10:05 PMAPASS
Permit finaled. Simplex to provide as-builts.
BLD07-02706 FIRE-Final Inspection4/30/20085/1/20085/1/2008 1:34:37 PMAFAIL
Emergency lights and exit signs have not been installed on the second floor as shown on the approved electrical plans. The emergency lights have not been installed for the stairway. The door 122 does not have passage hardware installed as required.The doors in the occupied area that have keyed hardware need approved hardware installed. One emergency light in the warehouse did not operate. The "door to remain unlocked..." sticker needs installed at the east main exit door. The area at the bottom of the interior stairs needs emergency lighting installed. A fire extinguisher needs installed on the second floor. The tenant improvement drawings were not routed through scott therefore no notes are provided.
BLD07-02078 FIRE-Final Inspection5/1/20085/1/20085/1/2008 1:29:22 PMPPASS
Life safety passed.
BLD06-01266 FIRE-Final Inspection5/1/20085/1/20085/1/2008 12:26:11 PMAPASS
Life safety passed.
FIR08-00196 INSP-Sprinkler Rough-in4/30/20085/1/20085/1/2008 12:23:08 PMAPASS
The sprinkler piping is ok to cover
BLD08-00116 FIRE-Final Inspection4/30/20085/1/20085/1/2008 11:51:19 AMAFAIL
A fire alarm permit needs to be aquired for the new audio/visual added to the new separation wall. All other life safety items are passed.
BLD08-00115 FIRE-Final Inspection4/30/20085/1/20085/1/2008 11:47:38 AMAPASS
Life safety passed